Service Manual

3 Troubleshooting (continued)

Table 3-4(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

 

• Replace the main control board if necessary.

 

 

• If 120 vac is present on a call for heat and the boiler

 

 

pump is not operating, replace the pump.

Outlet MRHL

 

• If the system pump is a variable speed pump, ensure

(cont’d)

 

that the system flow is not less than the boiler flow.

(will require a manual

The outlet water temperature has exceeded

• If operating on something other than an outlet sensor,

reset once the condition

has been corrected. Press

the setting of the manual reset high limit.

check temperature setting of the main control board.

• If the optional manual reset high limit has tripped,

the RESET button on the

 

SMART SYSTEM display

 

check setting of the device.

to reset.)

 

• Check resistance of water sensors and compare to

 

 

Table 3-2A on page 35 of this manual. Replace

 

 

sensor if necessary.

 

 

• Replace high limit.

 

 

 

 

 

• Vent/air intake lengths exceed the maximum allowed

 

 

lengths. Refer to Section 3 - General Venting of the

Fan Low/High

 

Knight XL Installation and Operation Manual for

 

proper lengths.

OR

 

• Check for obstruction or blockage in the vent/air

Fan Speed Low/

The actual fan RPM is 30% lower than what

High

is being called for.

intake pipes or at terminations.

• Check the wiring connections at the fan and at the

(will require a manual

 

reset once the condition

 

main control board.

has been corrected. Press

 

• Replace the fan.

the RESET button on the

 

 

• Replace the main control board.

SMART SYSTEM display

 

to reset.)

 

 

Blown fuse.

• Replace fuse F2 on the control board, see page 33

 

 

of this manual.

 

 

 

 

 

GV/Relay

 

• Check wiring harness connection at the gas valve and

 

at the main control board.

Fail

 

 

 

(will require a manual

The main control board did not detect the

• Replace the gas valve wire harness.

reset once the condition

 

has been corrected. Press

gas valve.

• Replace the gas valve.

the RESET button on the

 

 

 

SMART SYSTEM display

 

• Replace the main control board.

to reset.)

 

 

 

 

 

Sensor Open

 

• Check the sensors and their associated wiring.

(will require a manual

 

Repair or replace the sensor or wiring if damaged.

 

 

reset once the condition

Either the inlet water or outlet water

• Measure the resistance of the sensors and compare

has been corrected. Press

the RESET button on the

temperature sensor has been disconnected.

the resistance to the tables on page 35 of this

SMART SYSTEM display

 

manual.

 

 

to reset.)

 

• Replace the sensor if necessary.

 

 

 

 

 

41

Page 41
Image 41
Lochinvar 400, 801 service manual Fan Low/High, Fan Speed Low, GV/Relay, Fail, Sensor Open

400, 801 specifications

The Lochinvar 801,400 is a cutting-edge solution in the realm of high-efficiency commercial water heating. This model represents a significant advancement in the design and functionality of water heaters, catering primarily to the demands of large-scale facilities like hotels, hospitals, and large industrial operations.

One of the standout features of the Lochinvar 801,400 is its impressive heating capacity, which can produce up to 801,400 BTUs, making it suitable for high-demand applications. This output is crucial for establishments that require a consistent supply of hot water, such as commercial kitchens and laundry facilities. The robust design ensures that it can handle peak demand periods without compromising performance.

Another significant aspect is the innovative use of advanced technology in its operation. The Lochinvar 801,400 integrates smart controls that enhance its efficiency and ease of operation. These controls allow for precise monitoring and adjustment of water temperatures, ensuring that the system operates within optimal parameters while maximizing energy savings. The intelligent monitoring system can provide real-time updates, making it easier for facility managers to keep track of performance and address maintenance needs proactively.

The construction of the Lochinvar 801,400 incorporates durable materials that not only enhance the longevity of the unit but also offer resistance to corrosion and wear. This durability translates into lower maintenance costs and an extended lifespan for the unit, making it a worthwhile investment for businesses.

Moreover, the Lochinvar 801,400 is designed with energy efficiency in mind. It boasts a high thermal efficiency rating, which reduces operational costs and minimizes the carbon footprint of heating operations. This efficiency is critical in today’s environmentally conscious market, where businesses are seeking to reduce their energy consumption and comply with strict regulations.

The design of the Lochinvar 801,400 also prioritizes safety, featuring innovative safety controls and fail-safes that protect both the unit and the users.

In summary, the Lochinvar 801,400 offers a combination of high capacity, advanced technology, durability, and energy efficiency, making it an excellent choice for commercial water heating solutions. As industries continue to evolve, the demand for reliable and efficient water heating solutions like the Lochinvar 801,400 will only increase.