Lochinvar 81-286 service manual Cont’d, Flame Sequence

Models: 81-286

1 48
Download 48 pages 21.87 Kb
Page 39
Image 39

Service Manual

3 Troubleshooting (continued)

Table 3-4(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

The unit has failed to prove main burner

• Verify that the plastic hose from the gas valve to the air

 

ignition after four (4) attempts.

inlet is connected and is not damaged.

 

 

• Verify that the vent/air intake pipes are correctly

 

 

installed and that there are no obstructions.

 

 

• Check for 24 vac to the gas valve at the 2-pin

 

 

connection on the side of the main control board during

 

 

the ignition attempt. If no voltage is present, replace

 

 

the main control board.

 

 

• If 24 vac is present at the main control board, check

 

 

the wiring between the main control board and the gas

 

 

valve. Replace the wiring if necessary. Do not

 

 

disconnect the wiring from the gas valve and attempt to

Flame Fail Ign

 

measure voltage at that point. The main control board

 

can detect if the gas valve is not connected and will

(cont’d)

 

display the Gas Valve or Gas Valve Fail fault.

(will require a manual

 

• If 24 vac is present, check the outlet of the valve to

reset once the condition

 

ensure the valve is flowing gas. With a manometer

has been corrected.

 

connected to the outlet tap of the gas valve, when the

Press the RESET button

 

unit is in the prepurge period, there should be a

on the SMART SYSTEM

 

negative pressure present. When the valve is

display to reset.)

 

energized a change in pressure should occur. If the

 

 

pressure change does not occur, the gas valve is not

 

 

opening. Replace the gas valve.

 

 

• Inspect flame sensor and associated wiring.

 

 

Reference page 31 of this manual for removal and

 

 

cleaning procedures. Replace if necessary.

 

 

• Inspect and clean the heat exchanger as necessary.

 

 

Reference page 32 of this manual for cleaning

 

 

procedures.

 

 

• Inspect the burner. Reference page 31 of this manual

 

 

for removal and cleaning procedures. Replace if

 

 

necessary.

 

 

• Replace the main control board.

 

 

 

Flame Sequence

 

• Check supply voltage for proper polarity.

(will require a manual

 

• Check external wiring for voltage feedback.

reset once the condition

The flame detector circuit is seeing a flame

• Check the flame rod and make sure it is clean.

has been corrected.

signal while no flame is present.

Press the RESET button

• Check the internal wiring for bad connections.

on the SMART SYSTEM

 

 

• Replace main control board.

display to reset.)

 

 

 

 

39

Page 39
Image 39
Lochinvar 81-286 service manual Cont’d, Flame Sequence

81-286 specifications

Lochinvar 81-286 is a highly efficient and innovative heating solution that represents the latest advancements in boiler technology. This model, part of Lochinvar's prestigious line-up, is designed for commercial applications, delivering superior performance while emphasizing energy efficiency and user-friendly operation.

One of the standout features of the Lochinvar 81-286 is its robust construction. Built with high-quality materials, the unit is engineered for durability and reliability, ensuring long-term operation with minimal maintenance. Its compact design allows for versatility in installation, making it suitable for various building layouts and configurations.

The boiler's primary technology is its advanced condensing capability, which optimizes heat transfer and reduces energy consumption. By efficiently using the heat generated during combustion, the 81-286 can achieve higher thermal efficiencies, often surpassing traditional systems. This results in lower operating costs and reduced greenhouse gas emissions, aligning with the growing demand for sustainable energy solutions in commercial buildings.

Lochinvar incorporates intelligent control systems into the 81-286, featuring user-friendly interfaces that facilitate straightforward programming and monitoring. These control systems enable precise regulation of temperature and pressure, ensuring optimal operation while providing real-time feedback that aids in troubleshooting and maintenance. Users can enjoy the convenience of remote monitoring, enhancing the overall user experience.

Another key characteristic of the Lochinvar 81-286 is its capacity range. The model is available in various sizes, allowing it to meet the specific demands of different facilities, from small businesses to large industrial applications. This flexibility makes it a top choice for contractors and engineers seeking reliable heating solutions that cater to diverse needs.

In addition, the Lochinvar 81-286 boasts exceptional safety features, including built-in safeguards that protect against overheating and pressure surges. These aspects ensure that the unit operates within safe parameters, providing peace of mind for facility managers and operators.

In summary, the Lochinvar 81-286 combines durability, efficiency, and advanced technology, making it an ideal solution for commercial heating needs. With its innovative condensing design, intelligent controls, and safety features, this boiler stands out as a reliable choice for those seeking sustainable and effective heating solutions. Its versatility and performance make it a key player in today’s ever-evolving energy landscape.