![](/images/new-backgrounds/1052316/5231647x1.webp)
Service Manual
1 Service
Ramp Settings |
|
|
|
| Control modes |
| |
| Please note that the brackets ([]) denote | Controlling Sensor |
| ||||
NOTICE |
| ||||||
screen status. |
|
|
|
|
| ||
|
|
|
| The SH controlling sensor parameter selects the sensor the | |||
|
|
|
|
| |||
The SMART SYSTEM control can be programmed to limit | control will use to regulate the boiler firing rate. This parameter | ||||||
is adjustable by the installer by accessing the Controlling Sensor | |||||||
the firing rate for a fixed period of time at the start of a | |||||||
parameter. The sensor selections are as follows: | The outlet | ||||||
space heating demand. There are six (6) possible limits, | |||||||
sensor regulates the firing rate based on the outlet water | |||||||
each with their own time delay. The first limit applies as | |||||||
temperature of the boiler and the inlet sensor regulates the | |||||||
soon as the burner starts. Once its time delay expires, the | |||||||
firing rate based on the inlet water temperature of the boiler. | |||||||
second limit is applied and its timer begins. The control | |||||||
If the outlet sensor is selected, and the optional system supply | |||||||
steps through these limits until the 6th (sixth) limit expires. | |||||||
sensor is connected, the control will regulate the | firing rate | ||||||
Note, however, that the 6th limit will also limit the rate for | |||||||
based on the system supply sensor temperature. The default | |||||||
the rest of that heat demand. The installer can adjust the | |||||||
sensor is the Outlet Sensor. |
| ||||||
firing limits and time delays by accessing the Ramp Settings |
| ||||||
|
| ||||||
parameter. Once this parameter is selected, the screen will | BMS Thermostat Input |
| |||||
show the step number, the time delay for that step and the | When controlling the boiler through the 0 - 10V BMS input or | ||||||
limit value corresponding with that step. If the installer | |||||||
through ModBus, the boiler can be enabled one of two ways. | |||||||
wishes to adjust one of the values in that step, he can press | |||||||
With the BMS Thermostat Input parameter set to ACTIVE, | |||||||
the NAVIGATION dial until the value he wishes to change | |||||||
the boiler will be enabled by closing the Heat/Loop Demand 1 | |||||||
is flashing. The installer can then rotate the NAVIGATION | |||||||
input. When set to INACTIVE, the boiler will be enabled by the | |||||||
dial to adjust that value. If the installer | presses the RIGHT | ||||||
voltage level on the 0 - 10V input (in the case of 0 - 10V BMS | |||||||
SELECT [SAVE] key while the | limit | value is | flashing, | ||||
control), or the 0 - 10V input value received through ModBus. | |||||||
the step value will flash again. | The | installer | can then | ||||
The default value is INACTIVE. |
| ||||||
select the next step and adjust the delay and limit values |
| ||||||
|
| ||||||
corresponding with that step. |
|
|
| BMS |
| ||
When finished, the installer can press the RIGHT SELECT | The set point or modulation of the boiler may be controlled | ||||||
[SAVE] key to store the new settings, or the LEFT SELECT | through the 0 - 10V BMS input or through ModBus. When the | ||||||
[EXIT] key to return to the | BMS parameter is set to INACTIVE, the 0 - 10V input will be | ||||||
without saving the changes. The delay value can be set | ignored. When set to ACTIVE, the set point or modulation will | ||||||
between 0 minutes and 20 minutes. The limit value can be | be controlled by the voltage on the 0 - 10V input (in the case | ||||||
set between 0% and 100%. |
|
|
| of 0 - 10V BMS control), or the 0 - 10V input value received | |||
|
|
|
|
| through ModBus. The default value is INACTIVE. |
|
Figure 1-2 Ramp Delay Interval
24