Set Point
The Set Point knob specifies the target water temperature in degrees, Fahrenheit. After the water temperature reaches the set point, the temperature control shuts off the burners.
Differential
The Differential specifies the number of degrees below the set point that the control will allow the water temperature to drop before it brings the appliance back on again.
High-Fire Offset
The temperature control operates a
The
The
No matter what the
OUTDOOR AIR RESET OPTION
Outdoor Air Reset Option
For boilers ordered with the Outdoor Air Reset option, there is an additional control (FIG. 6). There are three setting knobs for Shutdown, Outdoor Air Max., and Ratio. There is also a switch to turn the outdoor air shutdown feature On or Off. An O.A. Sensor is also included.
(c)2002 L.C. |
| 55 |
|
|
| CN1 |
|
|
|
|
| CN2 | CN3 |
| |
CN7 |
| 50 | 60 |
|
|
|
|
|
|
|
| OJ1 | |||
|
|
|
|
|
|
|
|
|
| ||||||
CN8 | D4 | 45 |
| 65 |
| O.A. SENSOR |
|
|
|
|
| CN4 | C10 | ||
|
|
| ON ENABLE |
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
| VR3 |
|
|
| SW1 |
|
|
|
|
|
|
|
|
| W1 | 40 | 70 |
|
| DISABLE |
|
|
|
|
| CN5 | OJ2 | ||
| SHUTDOWN |
| O.A. SHUTDOWN |
|
| R6 R4 C7 | |||||||||
|
|
|
|
|
|
|
|
|
|
| |||||
|
| 50 | 55 | 60 |
| 0.80.9 1.01.11.2 | CN6 | C9 | |||||||
|
| 45 |
| 65 |
| 0.7 |
|
| 1.3 |
| W3 | J4 |
| ||
|
|
| VR1 |
|
| 0.6 | VR2 |
| 1.4 |
|
| R8 |
| ||
|
| 40 | 70 |
|
| 0.5 | 1.5 |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| ||||||
CN1 |
|
|
|
|
|
| W1 | W2 |
|
| |||||
| O.A. MAX. |
|
| RATIO |
|
|
|
|
|
| |||||
| 160 |
|
|
|
|
|
|
| CN9 | ||||||
|
|
|
|
| 9 | 10 11 |
|
|
|
| 10 |
| |||
|
| 200 |
|
|
|
|
|
|
| ||||||
140 |
|
| 8 |
|
| 12 |
|
|
| 5 |
| 15 | |||
|
|
|
|
|
| 13 | R15 | R16 |
| ||||||
|
|
|
| 220 | 7 |
|
|
|
|
|
| ||||
|
|
|
|
|
| 14 |
|
|
|
| |||||
120 |
|
|
|
| 6 |
|
|
|
|
|
|
|
| ||
|
|
|
| 5 | VR2 | 15 |
|
| VR3 | 20 |
| ||||
|
|
| 240 |
|
|
|
| ||||||||
| OFF | DIFFERENTIAL |
|
|
|
| |||||||||
| SETPOINT |
|
| TST2314 |
|
|
|
| OFFSET |
|
FIG. 6 Optional Outdoor Air Reset Control
Shutdown
The Shutdown knob specifies the outdoor air lockout temperature at which the control would prevent the appliance from operating.
Outdoor Air Max (O.A. Max)
The O.A. Max knob allows a reset up to the maximum outdoor air temperature specified by this knob setting. At any outdoor air temperature above the specified setting, the appliance will not reset but will continue to run at the set point temperature.
Ratio
The Ratio knob allows control over the reset ratio to be used during Outdoor Air Reset. The allowable ratios are as low as 0.5:1 or as high as 1.5:1.
Selecting the 0.5:1 ratio will increase the set point 0.5°F for every 1.0°F drop in outdoor air temperature up to the maximum set point temperature.
Selecting the 1.5:1 ratio will increase the set point 1.5°F for every 1.0°F drop in outdoor air temperature up to the maximum set point temperature.
See Figure 7 for an outdoor air reset chart example.
FIG. 7 Outdoor Air Control Example Chart
Outdoor Air Shutdown Enable/Disable Switch
The Outdoor Air Shutdown Enable/Disable switch turns the outdoor air shutdown feature On and Off. Disabling the Outdoor Air Shutdown feature allows the appliance to operate regardless of the outdoor air temperature. This is needed for indirect domestic hot water systems for example.
7