| TROUBLE SHOOTING GUIDE | ||
PROBLEM | CAUSE | SOLUTION | |
|
|
| |
No hot water | Boiler does not operate | Refer to boiler installation instructions | |
at faucet |
|
| |
| Check main service switch | ||
|
| ||
|
|
| |
|
| Check fused disconnect | |
|
|
| |
| Circulator does not operate | Check power supply | |
|
|
| |
|
| Replace as necessary | |
|
|
| |
| Improper aquastat setting calibration | Turn tank aquastat to appropriate or setting | |
|
|
| |
| Zone valve does not open (if used) | Check power supply | |
|
|
| |
|
| Replace as necessary | |
|
|
| |
| Electrical problem (relay, wiring, etc.) | Check fuse and replace | |
|
|
| |
|
| Check circuit breaker andreset (if applicable) | |
|
|
| |
|
| Check power supply | |
|
|
| |
| Scale | If boiler, circulator, and tank are operating | |
|
| satisfactorily, coil may have scale coating. | |
|
| See Maintenance | |
|
|
| |
| Clogged cold water filter or | Clean or replace filter or strainer | |
| boiler supply strainer (if used) |
| |
|
|
| |
Water at | Aquastat set too high | Lower aquastat setting. See Operating Instructions | |
faucet too |
|
| |
Improper system plumbing | Compare to plumbing in Water Connections | ||
hot | |||
|
|
| |
| Improper system wiring | Compare to wiring in Electrical Connections | |
|
|
| |
Insufficient | Aquastat setting too low | Adjust aquastat to higher setting. | |
hot water |
| See Operating Instruction | |
|
|
| |
| Undersized boiler with no | Rewire for priority | |
| priority to domestic hot water |
| |
|
|
| |
| Peak use of hot water is greater | Determine peak usage and compare to tank capacity | |
| than tank storage capacity |
| |
|
|
| |
| Faulty tank aquastat | Replace aquastat | |
|
|
| |
Boiler cycles | Excessive demand | Reduce demand or consider larger tank | |
more per day |
|
| |
|
| ||
in summer | Faulty aquastat | Replace aquastat | |
|
|
| |
| Boiler high limit set too low | Increase boiler high limit setting | |
|
|
|