2 Pre-installation

1.The installation must conform to the instructions in this manual and all applicable local, state, provincial, and national codes, laws, regulations, and ordinances. Installations in Canada must conform to B149.2 Installation Code.

2.Be certain the domestic water supply to the tank has physical and chemical characteristics that fall within the limits shown in Table 2A. Where questions exist as to the composition of the water on the job, a qualified water treatment expert should be consulted.

CAUTION

Water with characteristics outside the

limits shown in Table 2A may severely

 

 

shorten the life of the tank due to

 

corrosion. Damage to tanks in such

 

cases is not covered under warranty.

3.Read and understand all installation requirements in this manual.

Table 2A

Water Chemistry Requirements

Water used in the tank must have characteristics falling within the following limits:

Characteristic

Min.

Max.

 

 

 

Ph

6.0

8.0

 

 

 

Chloride (PPM)

--

80

 

 

 

Installation & Operation Manual

Locating the tank

1.Choose a location for your water heater centralized to the piping system. You must also locate the SIT water heater where it will not be exposed to freezing temperatures. Additionally, you will need to place the water heater so that the controls, drain, and inlet/outlets are easily accessible. This appliance must not be installed outdoors, as it is certified as an indoor appliance, and must also be kept vertical on a level surface.

2.Keep distance between boiler and water heater to a minimum to:

a.reduce piping heat loss

b.provide minimal friction loss

3.Figure 1-1 on page 4 shows the weights of all the tanks filled with water. Make sure that the location chosen for the tank is capable of supporting it.

CAUTION

This appliance must be placed where leakage

from the relief valve, leakage from the

 

 

related piping, or leakage from the tank or

 

connections, will not result in damage to the

 

surrounding areas, or to the lower floors of

 

the building. A water heater should always

 

be located in an area with a floor drain or

 

installed in a drain pan suitable for water

 

heaters. Lochinvar shall not be held liable for

 

any such water damage.

4.The tank may be located some distance from the boiler provided the pump is designed to provide the flow called for in Table 3B - Pressure Drop Values, through the coil. Also, the further the tank is from the boiler, the longer the response of the boiler will be to a call from the tank zone. Insulate piping between the boiler and the tank.

￿WARNING Failure to properly support the tank could result in property damage or personal injury.

Recommended clearances

The installation location must provide adequate clearances for servicing and proper operation of the water heater. A 12 inch vertical clearance is recommended from the top of the water heater. A zero clearance is allowed for the sides of the water heater. However, boiler and servicing clearances must be figured when locating the water heater.

5

Page 5
Image 5
Lochinvar SIT030, SIT119 Pre-installation, Locating the tank, Recommended clearances, Water Chemistry Requirements

SIT030, SIT119 specifications

Lochinvar is a renowned manufacturer of high-efficiency heating solutions, including a range of commercial and residential boilers. Among their offerings are the Lochinvar SIT119 and SIT030 models, which exemplify the brand's commitment to innovation and efficiency in modern heating systems.

The Lochinvar SIT119 is designed for medium to large residential applications, boasting a powerful heating capacity. This model features a robust stainless steel heat exchanger that not only enhances durability but also promotes optimal heat transfer. As part of Lochinvar’s commitment to energy efficiency, the SIT119 incorporates advanced features such as a modulating burner system that adjusts the flame output based on the heating demand, resulting in lower energy consumption and reduced operational costs.

In addition to its efficiency, the SIT119 is equipped with user-friendly controls that allow homeowners and technicians to easily manage and monitor the system. Its intuitive digital display provides real-time information on system performance and diagnostic capabilities, facilitating maintenance and troubleshooting. Furthermore, the SIT119’s compact design enables versatile installation options, making it suitable for various residential spaces.

On the other hand, the Lochinvar SIT030 is tailored for smaller residential applications. Despite its smaller size, it doesn’t compromise on performance or efficiency. This model also features a high-quality stainless steel heat exchanger, ensuring longevity and consistent heating performance. Like the SIT119, the SIT030 utilizes a modulating burner system to optimize energy use, making it an environmentally friendly choice for homeowners seeking effective heating solutions.

One notable characteristic of the SIT030 is its low NOx emission design, which aligns with contemporary environmental standards and helps reduce the carbon footprint associated with heating. Additionally, both models support easy integration with existing heating systems and can be paired with renewable energy sources, such as solar thermal systems, maximizing their efficiency and sustainability.

In summary, the Lochinvar SIT119 and SIT030 models stand out in the heating market, combining advanced technologies with high efficiency and user-friendly features. Their stainless steel construction, modulating burners, compact design, and emissions compliance make them excellent choices for homeowners looking to invest in reliable and eco-conscious heating solutions. With these models, Lochinvar continues to lead in producing innovative products that meet the evolving demands of the heating industry.