CAUSE C

Thermostats may not be functioning correctly or may be improperly set.

SOLUTION - Inspect thermostats for proper operation and correct settings. If setting is below the maximum, reset to 190ºF(88ºC) If defective and not functioning, replace.

CAUSE D

Contactors are not performing.

SOLUTION - Inspect contactors for proper operation by visual observation. Assuming no fuses are blown and power is coming to the booster, inspect the coil and replace if defective.

CAUSE E

ECO (high temperature limit switch) may be defective.

SOLUTION - Check for proper operation and replace if defective.

CAUSE F

The fuse is blown.

SOLUTION - Replace fuse. If fuse continues to blow, either a contactor coil is defective, or the booster control transformer is defective. If booster has more than one contactor, disconnect wires so only one contactor at a time is energized. The defective one can then be isolated and replaced.

On all boosters with low water cut-off, the following trouble shooting procedures apply.

CAUSE G

Relay does not pull in after booster is filled with water and air bled out.

SOLUTION

1.Check for voltage at line terminals 1 and 2 using volt-meter or test light. If there is no voltage, refer to CAUSE F.

2.Open circuit between ground and the probe. Check for broken wire or poor contact at connections. To test, run temporary wires from probe terminal #3. If relay pulls in, the wire is broken and should be replaced.

3.Check or open relay coils. With line voltage applied at 1 and 2, connect a jumper wire between 6 and 7. Relay should pull in when the jumper is connected and fall out when the jumper is removed. Failure to do so indicates one of the coils is open and the relay should be replaced.

4.Fouled probe. If solution 2 discloses no broken wire or poor connection and relay still does not pull in, probe tip may be insulated by lime buildup. If relay operates when a jumper wire is connected between terminals 3 and ground, the probe is fouled. Remove probe and clean the electrode.

TEMPERATURE REACHES ONLY 170-175ºF (77ºC - 79ºC). THIS CONDITION AS DIFFERENTIATED FROM CONDITION II INDICATES THE BOOSTER HEATER IS FUNCTIONING, BUT MAY NOT BE REACHING PROPER TEMPERATURE (180ºF, 82ºC).

CAUSE A

Booster should be close to the dishwasher, (5 feet or less). If the booster is more than 5 feet away, the heat loss through the pipes is the most likely reason the dishwasher thermometer reads only 170ºF

(77ºC). Make certain the thermostats are set to their maximum calibration. They are pre-set at the factory to 190ºF (88ºC) to compensate for heat loss but they may have been turned down to 180ºF (82ºC) by someone overlooking heat loss through the pipes.

SOLUTION - The booster should be moved to within 5 feet of the dishwasher if possible, and the pipes should be insulated.

CAUSE B

Thermostats may not be functioning correctly.

NOTE:

To help determine this cause, check rinse temperature in the dishwasher. Since the dishwasher temperature gauge could become defective, it is preferable to rely on a temperature sensitive tape or a thermometer rather than the gauge for checking this cause.

SOLUTION - If maximum reading is below 180ºF, (82ºC) first turn the pointers all the way up on all thermostats. If the reading is still below 180ºF (82ºC), minor adjustments can be made on the thermostats. If recalibration does not help, the thermostat is defective and should be replaced.

BOOSTER HEATER REPEATEDLY BLOWS FUSES OR TRIPS CIRCUIT BREAKERS.

NOTE:

Fuses or circuit breakers should not be loaded to more than 80% of their rating.

CAUSE A

Fuses are undersized-too small to carry the load.

SOLUTION - Check “Fuse and Disconnect Switch Sizes” table for recommended sizes. Replace undersized fuses with correct one.

CAUSE B

Short circuit in internal heater wiring.

SOLUTION - By visual inspection check for: loose connections, grounded heating elements, frayed insulation and foreign matter touching wiring terminals.

WHEN THE DISHWASHER AND THE BOOSTER HAVE BEEN IDLE FOR SEVERAL HOURS, RELIEF VALVE OPENS OR ECO TRIPS.

CAUSE A

A cause of overheating and resulting relief is excessive primary water temperature. Primary water temperature should not exceed 160ºF (71ºC).

SOLUTION - Check to be sure primary water heater is functioning properly. Primary water heater thermostats may be set too high, causing nuisance tripping. Adjust primary heater thermostats to 140-150ºF (60ºC - 66ºC).

4

Page 4
Image 4
Lochinvar SSB-i & s--01 installation instructions Cause F, Cause G

SSB-i & s--01 specifications

Lochinvar has established itself as a leader in the field of high-efficiency heating solutions, and its SSB-i and S--01 models exemplify the brand’s commitment to innovation and performance. These systems are designed for both residential and commercial applications, providing versatile solutions to meet a range of heating demands.

The Lochinvar SSB-i series features a robust stainless steel heat exchanger, ensuring durability and longevity. This series is engineered to achieve outstanding thermal efficiency, often exceeding 95%, which significantly reduces energy consumption and operational costs. The advanced technology utilized in the SSB-i includes modulating burners that automatically adjust to the heating demands, providing consistent comfort while minimizing fossil fuel usage.

On the other hand, the S--01 model stands out with its space-saving design, making it ideal for installations where room is limited. The S--01 maintains high efficiency through its innovative design that promotes optimal air and fuel mixing, which leads to cleaner combustion and reduced emissions. It is also equipped with an advanced control system that allows for precise monitoring and adjustments, ensuring that the heating system operates at its best regardless of external conditions.

Both models come equipped with user-friendly digital interfaces, allowing homeowners and facility managers to easily program and control settings. This integration of smart technology means users can manage their heating systems remotely, enhancing energy efficiency and convenience. Additionally, Lochinvar has incorporated advanced safety features such as flame safeguards and high limit controls in both models, offering peace of mind and operational reliability.

The SSB-i and S--01 units are also compatible with various renewable energy sources, such as solar thermal systems, making them an environmentally friendly choice. Their compact size and flexibility in installation options mean they can seamlessly fit into a variety of spaces, whether retrofitting an existing system or as part of a new construction project.

In summary, the Lochinvar SSB-i and S--01 models showcase the company’s dedication to efficient, sustainable, and reliable heating solutions. With their advanced technologies, user-friendly features, and focus on safety and efficiency, these systems are an excellent investment for those looking to improve their heating capabilities while minimizing their environmental footprint.