CIRCUIT BREAKER AND FUSED DISCONNECT SWITCH SIZES
kW | VOLTS | PH | L1 | L2 | L3 | Breaker or Fuse Size | Copper Wire Size | Conduit Size |
6 | 208 | 1 | 29 | 29 | — | 40 | 8 | 1/2” |
| 208 | 3 | 14 | 25 | 14 | 40 | 8 | 3/4” |
| 240 | 1 | 25 | 25 | — | 40 | 8 | 1/2” |
| 240 | 3 | 13 | 22 | 13 | 30 | 10 | 1/2” |
| 480 | 3 | 6 | 11 | 6 | 15 | 14 | 1/2” |
9 | 208 | 1 | 43 | 43 | — | 60 | 6 | 3/4” |
| 208 | 3 | 22 | 38 | 22 | 50 | 8 | 3/4” |
| 240 | 1 | 38 | 38 | — | 50 | 8 | 1/2” |
| 240 | 3 | 19 | 33 | 19 | 50 | 8 | 3/4” |
| 480 | 3 | 9 | 16 | 9 | 20 | 12 | 1/2” |
12 | 208 | 1 | 58 | 58 | — | 90 | 3 | 1” |
| 208 | 3 | 33 | 33 | 33 | 50 | 8 | 3/4” |
| 240 | 1 | 50 | 50 | — | 70 | 4 | 1” |
| 240 | 3 | 29 | 29 | 29 | 40 | 8 | 3/4” |
| 480 | 3 | 14 | 14 | 14 | 20 | 12 | 1/2” |
15 | 208 | 1 | 72 | 72 | — | 90 | 3 | 1” |
| 208 | 3 | 42 | 42 | 42 | 60 | 6 | 3/4” |
| 240 | 1 | 63 | 63 | — | 90 | 3 | 1” |
| 240 | 3 | 36 | 36 | 36 | 50 | 8 | 3/4” |
| 480 | 3 | 18 | 18 | 18 | 30 | 10 | 1/2” |
18 | 208 | 1 | 87 | 87 | — | 125 | 1 | |
| 208 | 3 | 48 | 48 | 48 | 60 | 6 | 3/4” |
| 240 | 1 | 75 | 75 | — | 100 | 3 | 1” |
| 240 | 3 | 43 | 43 | 43 | 60 | 6 | 3/4” |
| 480 | 3 | 22 | 22 | 22 | 30 | 10 | 1/2” |
24 | 208 | 1 | 115 | 115 | — | 150 | 1/0 | |
| 208 | 3 | 67 | 67 | 67 | 90 | 3 | |
| 240 | 1 | 100 | 100 | — | 125 | 1 | |
| 240 | 3 | 58 | 58 | 58 | 90 | 3 | |
| 480 | 3 | 30 | 30 | 30 | 40 | 8 | 3/4” |
30 | 208 | 1 | 144 | 144 | — | 200 | 3/0 | |
| 208 | 3 | 83 | 83 | 83 | 125 | 3 | |
| 240 | 1 | 125 | 125 | — | 175 | 2/0 | |
| 240 | 3 | 72 | 72 | 72 | 100 | 3 | |
| 480 | 3 | 36 | 36 | 36 | 50 | 8 | 3/4” |
36 | 208 | 1 | 173 | 173 | — | 225 | 4/0 | 2” |
| 208 | 3 | 100 | 100 | 100 | 125 | 1 | |
| 240 | 1 | 150 | 150 | — | 200 | 3/0 | |
| 240 | 3 | 87 | 87 | 87 | 125 | 1 | |
| 480 | 3 | 43 | 43 | 43 | 60 | 6 | 3/4” |
45 | 208 | 3 | 125 | 125 | 125 | 175 | 2/0 | 2” |
| 240 | 1 | 188 | 188 | — | 250 | 250 MCM | 2” |
| 240 | 3 | 108 | 108 | 108 | 150 | 1/0 | |
| 480 | 3 | 54 | 54 | 54 | 70 | 4 | 1” |
54 | 208 | 3 | 150 | 150 | 150 | 200 | 3/0 | |
| 240 | 3 | 130 | 130 | 130 | 175 | 2/0 | 2” |
| 480 | 3 | 65 | 65 | 65 | 90 | 3 | |
58 | 208 | 3 | 162 | 162 | 162 | 225 | 4/0 | 2” |
| 240 | 3 | 141 | 141 | 141 | 200 | 3/0 | |
| 480 | 3 | 71 | 71 | 71 | 90 | 3 |
Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers are to be mounted remotely and wired by the contractor. Sizes are based on the NEC table