Lochinvar SSB-i & s--01 Circuit Breaker And Fused Disconnect Switch Sizes, Breaker or Fuse Size

Models: SSB-i & s--01

1 12
Download 12 pages 16.6 Kb
Page 7
Image 7
CIRCUIT BREAKER AND FUSED DISCONNECT SWITCH SIZES

CIRCUIT BREAKER AND FUSED DISCONNECT SWITCH SIZES

kW

VOLTS

PH

L1

L2

L3

Breaker or Fuse Size

Copper Wire Size

Conduit Size

6

208

1

29

29

40

8

1/2”

 

208

3

14

25

14

40

8

3/4”

 

240

1

25

25

40

8

1/2”

 

240

3

13

22

13

30

10

1/2”

 

480

3

6

11

6

15

14

1/2”

9

208

1

43

43

60

6

3/4”

 

208

3

22

38

22

50

8

3/4”

 

240

1

38

38

50

8

1/2”

 

240

3

19

33

19

50

8

3/4”

 

480

3

9

16

9

20

12

1/2”

12

208

1

58

58

90

3

1”

 

208

3

33

33

33

50

8

3/4”

 

240

1

50

50

70

4

1”

 

240

3

29

29

29

40

8

3/4”

 

480

3

14

14

14

20

12

1/2”

15

208

1

72

72

90

3

1”

 

208

3

42

42

42

60

6

3/4”

 

240

1

63

63

90

3

1”

 

240

3

36

36

36

50

8

3/4”

 

480

3

18

18

18

30

10

1/2”

18

208

1

87

87

125

1

1-1/4”

 

208

3

48

48

48

60

6

3/4”

 

240

1

75

75

100

3

1”

 

240

3

43

43

43

60

6

3/4”

 

480

3

22

22

22

30

10

1/2”

24

208

1

115

115

150

1/0

1-1/4”

 

208

3

67

67

67

90

3

1-1/4”

 

240

1

100

100

125

1

1-1/4”

 

240

3

58

58

58

90

3

1-1/4”

 

480

3

30

30

30

40

8

3/4”

30

208

1

144

144

200

3/0

1-1/2”

 

208

3

83

83

83

125

3

1-1/2”

 

240

1

125

125

175

2/0

1-1/2”

 

240

3

72

72

72

100

3

1-1/4”

 

480

3

36

36

36

50

8

3/4”

36

208

1

173

173

225

4/0

2”

 

208

3

100

100

100

125

1

1-1/2”

 

240

1

150

150

200

3/0

1-1/2”

 

240

3

87

87

87

125

1

1-1/2”

 

480

3

43

43

43

60

6

3/4”

45

208

3

125

125

125

175

2/0

2”

 

240

1

188

188

250

250 MCM

2”

 

240

3

108

108

108

150

1/0

1-1/2”

 

480

3

54

54

54

70

4

1”

54

208

3

150

150

150

200

3/0

1-1/2”

 

240

3

130

130

130

175

2/0

2”

 

480

3

65

65

65

90

3

1-1/4”

58

208

3

162

162

162

225

4/0

2”

 

240

3

141

141

141

200

3/0

1-1/2”

 

480

3

71

71

71

90

3

1-1/4”

Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers are to be mounted remotely and wired by the contractor. Sizes are based on the NEC table 310-16. Conduit size is based on conductors plus ground wire sizing as per NEC table 250-122.

7

Page 7
Image 7
Lochinvar SSB-i & s--01 installation instructions Circuit Breaker And Fused Disconnect Switch Sizes, Breaker or Fuse Size