HEARTHVIEW FRAMING SPECIFICATIONS
Please refer to the Installation Manual for all installation information. Installation Manual can be downloaded from the Lopi website under the specific product
13 1 REAR VENT
Minimum Framing Dimensions - Rear Vent
A - Minimum 1/2” clearance
B - Minimum 1” clearance
C - 7 1/2” approximate, varies due to vent installation
D - Most installations use:
-6” vent section for 2 x 6 walls
-4” vent section for 2 x 4 walls
Firestop required (included with fireplace)
Vent clearance (8” dia. vent): 1” to the sides, 1” below and 3” above the vent to combustibles
B
A
Route the electrical line to a
30 3/4”
38”
Cposition at the left rear of the fireplace
38 1/2”
D
48” Min.
41 1/4”
TRV: Minimum enclosure height = 38 1/2”
HH: Minimum enclosure height = 49”
25 3/4”
20”
The on/off switch/thermostat wire (if used) should be routed to a location near the right front of the fireplace
Minimum2 TOPFramiVENTg Dimensions - Top Vent
Minimum 1/2” Clearance
48” | Min. | Route the electrical |
|
| line to a position at |
|
| the left rear of the |
|
| fireplace |
TRV: Minimum enclosure height = 38 1/2”
HH: Minimum enclosure height = 49”
Note: Improper installation of your gas appliance or failure to operate it in accordance to the guidelines detailed in the Installation Manual may negate your warranty and endanger your home and family. Installation information is available on our website at www.lopifire.com. We recommend all Lopi appliances be installed and maintained on an annual basis by your Specialty Hearth Retailer.
381/2”
41 1/4”
20”
The on/off switch/thermostat wire (if used) should be routed to a location near the right front of the fireplace