LST FTX-P1 manual Description, Building Safety. Building Security, Optical Filtrex Detector

Models: FTX-P1

1 2
Download 2 pages 27.59 Kb
Page 1
Image 1
Optical Filtrex Detector

Optical Filtrex Detector

FTX-P1

ADM loop technology with System Sensor/200 protocol

For use in heavily contaminated areas
Replaceable filter

Constant response sensitivity

Function testable with magnet

Description

The addressable Optical Filtrex Smoke Detector FTX-P1 uses the scattered light principle and was developed for the detection of smoke particles in heavily conta- minated areas. The detector is used, for example, in industrial plants where dust is released by production or cleaning.

By means of an integrated fan, air samples are drawn into the sensing chamber through two separate fi lters. The fan is powered by a separate 24VDC supply and operates in a 15% duty cycle (5 seconds on, 30 se- conds off), thus allowing low power consumption as well as precise evaluation of the air samples.

The fi lters are monitored for contamination. They are designed to let smoke reach the sensing chamber, whereas causes of deceptive alarms (dust particles and tiny drops of water) are kept away from it. The ou- ter fi lter is removeable and can be cleaned or replaced by the operator. The modern design of the sensing chamber allows to reliably evaluate the characteristics of fi re.

The proven ADM loop technology with System Sen- sor/200 protocol establishes a permanent communi- cation between the fi re detection control panel and the detector. That ensures a periodical function testing of the detector. In the control panel all types of fi res are detected by continuously comparing fi re patterns.

Intelligent evaluation algorithms use the current condi- tion of the sensing chamber to predict the likely time of the next maintenance. Thus the alarm threshold is automatically adjusted within the permissible range, depending on the contamination. With that, the con- stant response sensitivity of the detector is ensured for the duration of its usage.

The two LEDs with 360° visibility indicate the activated condition of the detector. The detector address is se- lected with two decadic rotary switches, thus allowing to change the detector without additional tools.

A detector function test can be conveniently conducted using a magnet or test gas. The detector is attached to the base B524FTXE.

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

FTX-P1_DBL_LST_EN_0804.PDF • PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 