Lucent Technologies EST-48 installation instructions CHIMNEY 30 OFFSET THROUGH FLOOR OR CEILING

Models: EST-48

1 20
Download 20 pages 4.43 Kb
Page 8
Image 8
Attic Above

Anchor Tab

Figure 17

Step 4. The fireplace should be secured to the side framing members using the nailing flange. Use 8d nails (Figure 18 ).

Nailing

Flange

Framing

 

Stud

8d Nail

Figure 18

Note: The nailing flange and the area directly behind the nailing flange is exempt from the clearances described on the fireplace clearance

CAUTION: ALLOW MINIMUM 2" CHIMNEY AIR SPACE TO COMBUSTIBLE FRAMING MEM- BERS THROUGHOUT VERTICAL OR OFFSET CHIMNEY INSTALLATION.

A minimum 2" air space must be reserved for all combustible materials extending for any continuous length surrounding the chimney.

Reference Figures 15 and 16 and charts Fram- ing Dimensions for Ceiling and Roof, which specify minimum ceiling and roof dimensions.

In new construction, to determine chimney cen- ter line, use plumb line from roof or ceiling above fireplace to center of flue collar on fireplace.

For remodeling, plumb to center of flue collar from ceiling above, drive nail through ceiling from below to mark position, then mark and cut to passage from above ceiling (around nail) (Figure 19 ). Then plumb from ceiling or roof level directly above hole which has just been completed.

Plumb Line

Room Above

Firestop Spacer

Figure 20

Attic Above

Firestop Spacer

Figure 21

CHIMNEY 30° OFFSET THROUGH FLOOR

OR CEILING

It may be necessary to assemble the chimney at 30° when passing through the floor or ceiling area. Use the F10FS30-2 firestop spacer as shown in Figures 22 and 23. Support the chimney at floor or ceiling penetration with a FTF10 stabilizer if distance of chimney below ceiling is 10' or more. Maintain 2" minimum air space to combustibles from chimney sections.

Attic Space

label.

Note: The nailing tabs and the area directly behind the nailing tabs are exempt from the clearances described on page 5. Maintain at least 1/2" clearance from the firebox wrapper to the framing at the closest point of contact, directly adjacent to the flange.

INSTALLING THE CHIMNEY SYSTEM

Figure 19

Step 3. Position appropriate firestop spacer at ceiling and nail temporarily with two (2) 8d nails. Use flat firestop spacer, Model F10FS-2, if chim- ney penetrates ceiling vertically. If chimney pen- etrates ceiling at 30° angle (offset chimney), use

F10FS30-2 Firestop Spacer

2" Min.

Air Space

2" Min.

Air Space

FTF10-S4

Stabilizer

10'

Max. 30° Firestop

And Attic Above

8

Step 1. Before continuing, check the operation of the damper, as described on page 4, (refer to Figure 3 ).

Step 2. Using standard construction framing techniques, construct opening for chimney route up through the ceiling(s) and roof or through an outside chase.

Framing must maintain adequate minimum air space clearance at all times.

30° firestop spacer, Model F10FS30-2. Use one nail on opposite sides to hold firestop spacer in position. Nail permanently, using at least two (2) more 8d nails, after chimney sections have been assembled through the firestop spacer and after any necessary adjustments have been made. Firestop spacer must be secured by at least four

(4) 8d nails when completely installed.

Note: If there is a room above ceiling level, firestop spacer must be installed on the bottom side of the ceiling. If an attic is above ceiling level, firestop spacer must be installed on top side of ceiling joist (Figures 20 and 21 ).

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Figure 22

Room Above

 

F10FS30-2

2" Min.

Firestop Spacer

 

Air Space

2" Min.

FTF10-S4

Air Space

Stabilizer

10'

30° Firestop

Max.

And Room Above

Figure 23

Page 8
Image 8
Lucent Technologies EST-48 CHIMNEY 30 OFFSET THROUGH FLOOR OR CEILING, Installing The Chimney System