Side Wall Protection

SR/SC Series "A" Woodburning Fireplace

Side Wall Protection

Hearth Installation

Adjacent combustible side walls that are within the mini- mum dimensions shown in Figure 23 of fireplace open- ing must be protected with MHSC Wall Shield Model SP40 or a specifically built wall shield described below.

The special wall shield design described in Figure 20 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.

Examples of wall shield insulation:

1.Manville - CERAFORM 126, K=.27, 1/2 inches thick

2.MHSC - EH2416, K = .458,

1 inch thick required.

A hearth extension is required to protect a combustible floor in front of the fireplace. Refer to Figure 23 for mini- mum dimensions and mounting detail.

NOTE: Hearth Extension must not cover the air inlet opening of a fireplace.

The hearth extension described in Figure 23 must be a durable noncombustible material with a minimum (total) Rt value of 1.09; refer to Figure 24 for examples. The overall height (above a combustible floor), depth and width must be as indicated, with the extension centered to the fireplace opening.

The top of insulation must be covered with a noncom- bustible decorative covering or a piece of .018” mini- mum sheet metal, to protect hearth extension material. (Fig. 23)

Secure the hearth extension to the floor to prevent shifting, using trim molding or other similar means at three (3) outer edges. Seal crack between the fireplace hearth and hearth extension with a noncombustible material. (Figs. 23 and 25)

Minimum Wall Clearances

WITH

 

WITHOUT

Noncombustible

 

Noncombustible

Surround Facing

 

Surround Facing

 

 

Shaded area starts

4" BRICK

 

1/2" away from

 

edge of unit.

(Example material)

 

 

4"

 

 

E F**

FIREBOX

E D

OPENING

 

 

C**

A - Min. clearance

 

 

to combustible

 

 

perpendicular wall

 

SIDE

B - Min. clearance

SIDE

WALL

to combustible

WALL

 

perpendicular wall when

 

using noncombustible wall shield*

Hearth Installation Combustible material permitted within shaded area.

*Noncombustible wall shield requires 1" MHSC EH2416 insulation (minimum R Value = 1.85) between decorative noncombustible rigid covering and combustible wall.

Minimum height and width is 40" x 40".

**Dimension/degree of angle will vary depending on thickness of noncombustible surround facing.

Minimum Hearth Extension Dimensions

(for On-Site Construction)

 

H

G

G

 

 

 

 

 

 

J

 

Seal cracks

 

 

May install

between the

 

noncombustible

fireplace

 

 

decorative

and hearth

 

 

covering

extension with

 

OR .018" min.

noncombustible

 

sheet metal

material

 

FIREPLACE

 

 

 

 

 

 

HEARTH

4" MIN.

 

 

 

COMBUSTIBLE

MINIMUM

Safety strips

FLOOR

INSULATION

must overlap

 

VALUE "R"

1/2" minimum

 

A

B

C

D

E

F

G

H

J

SR/SC36A

16"

12"

48°

41°

18"

14"

7³⁄"

16"

48"

 

406 mm

305 mm

 

 

457 mm

356 mm

197 mm

406 mm 1219 mm

SR/SC42A

20"

12"

42°

35°

18"

14"

11¹⁄"

20" 61¹⁄"

 

508 mm

305 mm

 

 

457 mm

356 mm

292 mm

508 mm 1562 mm

 

 

 

 

 

 

 

 

 

 

FP594

Fig. 23 Combustible side wall protection and hearth extension dimensions.