LDVR Series Direct Vent Gas Fireplace

Locating Your Fireplace

E

A

B

Y

 

 

 

 

C

X

 

 

D

 

Y

X

B

 

 

F

 

 

 

LU584-R

Fig. 2 Locate gas fireplace.

 

A) Flat on wall

B) Cross corner

C) **Island

D) *Room divider

E) *Flat on wall corner

F) Chase installation

Y) 6” minimum

 

 

NOTE: (Fig. 2)

**Island (C) and Room Divider (D) installation is possible as long as the horizontal portion of the vent system (X) does not exceed 20’ (610cm). See details in Venting Section.

*When you install your fireplace in(D) Room divider or (E) Flat on wall corner positions (Y), a minimum of 6” (153mm) clearance must be maintained from the perpendicular wall and the front side edge of the fireplace.

Refer to (Y) in Figure 2.

Clearance to Combustibles

Top of Unit to Ceiling

36” (914 mm)

Appliance

 

Top

0” (0 mm)

Bottom

0” (0 mm)

Side

0” (0 mm)

Back

0” (0 mm)

Venting

 

Concentric sections of DV Vent

 

Top, bottom & sides

1” (25 mm)

Rear Vent Applications:

 

Top

2” (50 mm)

Sides and Bottom

1” (25 mm)

Flex Vent

7/8” (22 mm)

Mantels

The height that a combustible mantel is fitted above the fireplace is dependent on the depth of the mantel. This also applies to the distance between the mantel leg (if fitted) and the fireplace.

For the correct mounting height and widths refer to Figs. 3a and 3b, and the following Mantel Charts.

The fitting of a bay window trim kit does not effect the distances and reference points referred to in the diagram and chart.

Noncombustible mantels and legs may be installed at any height and width around the appliance.

When using paint or lacquer to finish the mantel, such paint or lacquer must be heat resistant to prevent

discoloration.

6

V

W

X

Y

Z

 

 

 

 

 

 

 

 

 

 

3/4” (19 mm) Scribe

 

 

 

 

 

 

 

 

 

 

Moulding for use with

 

 

 

A B

C D

E

 

 

 

CFM Cabinets

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fireplace

 

 

 

 

 

 

 

 

 

 

 

 

 

Top Louvre

 

 

 

 

 

 

 

 

 

 

Assembly

 

 

 

 

 

 

 

 

 

 

Top of Combustion

 

 

 

 

 

 

 

 

 

 

Chamber

CFM146

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mantel Chart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mantel Shelf

 

 

 

 

 

 

Mantel from Top

Ref.

or Breast Plate

Ref.

 

 

of Combustion Chamber

 

 

Depth

 

36/39/43 LDVR

 

33LDVR

 

 

 

 

V

10”

(254 mm)

A

 

17”

 

(432 mm)

 

16¹⁄” (419 mm)

W

8”

(203 mm)

B

 

15”

 

(381 mm)

 

14¹⁄” (368 mm)

X

6”

(152 mm)

C

 

13”

 

(330 mm)

 

12¹⁄” (318 mm)

Y

4”

(102 mm)

D

 

11”

 

(279 mm)

 

10¹⁄” (267 mm)

Z

2”

(51 mm)

E

 

9”

 

(229 mm)

 

8¹⁄” (216 mm)

Fig. 3a Combustible mantel minimum installation.

 

 

3/4” (19 mm) Scribe

 

 

Moulding for use with

 

 

CFM Cabinets

 

Black

 

J

I H

 

 

 

G

Surround

 

 

 

Face

Mantel

 

 

F

 

 

 

 

CFM164a

Leg

 

 

 

Side of

 

MLK

 

 

Combustion Chamber

N

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mantel

 

Mantel Leg FromSide

 

Ref.

 

 

Leg Depth

Ref.

of Comb. Opening

 

F

 

 

10”

(254 mm)

K

11¹⁄

(292 mm)

 

G

 

 

8”

(203 mm)

L

9¹⁄

(241 mm)

 

H

 

 

6”

(152 mm)

M

7¹⁄

(191 mm)

 

I

 

 

4”

(102 mm)

N

5¹⁄

(140 mm)

 

J

 

 

2”

(51 mm)

O

3¹⁄

(89 mm)

 

 

 

 

 

 

 

 

 

 

Fig. 3b

Combustible mantel leg minimum installation.

 

 

 

 

 

 

 

 

 

 

10007317

Page 6
Image 6
Majestic Appliances LDVR1 Locating Your Fireplace, Clearance to Combustibles, Mantels, Mantel Chart