Installing the Firestop Spacer

SR/SC Series "A" Woodburning Fireplace

Continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must install a firestop spacer.

Installing the Firestop Spacer

in the Ceiling Hole

A firestop spacer is used to keep pipe spaced properly and required for safety.

Nail the firestop spacer (at each corner) to the framing members of the ceiling hole. NOTE: A firestop spacer is not required at the roof.

Hole sizes listed in Figure 13 for angled firestop spacers provide minimum required air space to chim- ney pipe for ceiling thickness up to 8" (203mm). When combined thickness of ceiling material, ceiling joists and flooring material exceeds 8" (203mm), adjustments must be made in framing to assure that minimum air spaces to chimney are maintained.

in the Ceiling Hole Pipe Section

Pipe

Rim

Proper Firestop Spacer Installation Hem

Canadian Requirements Lance

Pipe

Rim

FP558

Fig. 16 Install pipe, listening for the snap-lock to fasten.

Proper Firestop Spacer Installation

Figure 18 shows different installation procedures for both an area that is an attic and an area that is not an attic.

If the area above the ceiling is not an attic, position the firestop spacer with the flange on the ceiling side and the angled portion extending up into the hole.

If the area above the ceiling is an attic, position the firestop spacer with the flange on the top of the framed hole and the angled portion extending down into the hole.

Firestop spacers are not available for nor are they required on vertical walls.

DO NOT put any sealant around the area where the outer pipe slides through the firestop spacer. If you seal this area, it may cause a fire hazard.

Elbow Strap

Angled Strap

FP270/271

Support Structure

Elbow Strap (must be tight)

Ceiling Hole

Framing

for Insulation ShieldManual background Angle Firestop

Chimney Support Strap (must be tight)

Canadian Requirements

Fig. 17 Attach straps to a structural framing member.

 

for Insulation Shield

 

In Canada, an attic

Attic Installation

Ceiling Installation

insulation shield is

 

 

 

required to prevent attic

 

 

Nails (4)

insulation from contact-

 

 

 

 

Joist

ing the chimney sec-

 

 

 

 

Firestop

tion. Framing dimen-

 

 

 

 

Spacer

sions for the chimney

 

 

 

hole should measure

 

 

Firestop

14¹⁄₂" x 14¹⁄₂" (368 x

 

 

Spacer

 

 

Joist

368mm). An attic shield

 

 

 

 

 

MUST be installed on

 

 

 

top of attic joists (above

 

 

Nails (4)

the floor level). (Fig.

 

 

 

 

FP593

19)

 

 

Fig. 18

Installing firestop spacer.

 

 

 

12

 

 

7412948