Mamiya Econotig manual Electrical Service Guide, Connecting Input Power

Models: Econotig

1 32
Download 32 pages 63.94 Kb
Page 18
Image 18

5-4. Electrical Service Guide

S-0092J

.For 230 V models with wall receptacle, 100% duty cycle used to calculate data below. 20% duty cycle used for all other models.

Input Voltage

200

230

380

415

460

 

 

 

 

 

 

Input Amperes At Rated Output

60

52

39

36

33

 

 

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

 

 

 

 

Time-Delay 2

70

60

45

40

30

Normal Operating 3

90

80

60

50

40

Min Input Conductor Size In AWG 4

10

6

12

12

14

Max Recommended Input Conductor Length In Feet (Meters)

42

135

151 (46)

181 (55)

85 (26)

(13)

(41)

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG 4

10

8

12

12

14

Reference: 2005 National Electrical Code (NEC) (including article 630)

 

 

 

 

 

1Consult factory for circuit breaker applications.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).

4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

5-5. Connecting Input Power

Tools Needed:

When making connections in the line

L1

disconnect device, connect the Green

 

Or Green/Yellow ground conductor first.

 

All Other

Models

GND/PE

L2

Install conductors into a deenergized line disconnect device.

230Volt

Models Only

YHave only qualified persons make this installation.

YDisconnect and lockout/tagout input power before connecting input conductors for wall recep- tacle or from unit.

YSpecial installation may be required where gasoline or vola- tile liquids are present − see NEC Article 511 or CEC Section 20.

230 Volt Models:

Units come equipped with input power cord and plug. Wall receptacle is cus- tomer supplied. To install, select type and size input and grounding conduc- tors using Section 5-4. Conductor rating must comply with national, state, and local electrical codes.

Install and connect grounding conduc- tor and input conductors in conduit or equivalent between wall receptacle and deenergized line disconnect device.

All Other Models:

Units come equipped with input power cord for installation into line disconnect device. Select type and size overcur- rent protection using Section 5-4.

GND/PE

L1

L2

230 VAC, 1

ST-161 454-A

OM-303 Page 14

Page 18
Image 18
Mamiya Econotig manual Electrical Service Guide, Connecting Input Power