Marquis Everyday Hot Tub owner manual Installation instructions

Models: Everyday Hot Tub

1 29
Download 29 pages 24.03 Kb
Page 14
Image 14

get into it!

installation instructions

Ground Fault Circuit Interrupters (GFCI) are available from your Marquis Spas dealer.

240 Volt:

All connections must be made in accordance with the wiring diagram found on the inside of the control box cover. Connections must be made with copper conductors only – do not use aluminum wiring with

this system. All conductors, circuit breakers, and/or fuses must be sized in accordance to the total amperage load as specified:

• Permanently connected

• Rated 240V, 60 Hz, 50A, three wires (#6 copper) plus ground (#8 AWG copper)

• Fuse or circuit breaker size: 50 amp

For units for use in other than single- family dwellings, a clearly labeled emergency switch shall be provided as part of the installation. The switch shall be readily accessible to the occupants and shall be installed adjacent to, within sight of, and at least five feet (1.52 m) from the spa.

This equipment is designed to operate on 60Hz alternating current only at a voltage of 240 (+ or -). Units to be operated at 240V must have all connec- tions made by a qualified electrician in accordance with all electric codes in effect at the time of installa- tion. All 240V units require four wires (line 1, line 2, neutral, and ground). Refer to the label at the terminal block.

NOTE: Ensure the GFCI is properly installed. Failure to do so may result in spa malfunction or damage which is not warranted.

A pressure wire connector is located on the exterior of the control box. This pressure wire connector should be bonded with at least #8 AWG (8.42mm2, #6 in Canada) copper wire to any metal ladder, metal water pipe, common bonding grid (reinforced con- crete slab, ground plate beneath the spa), or any other metal within five feet of the spa.

14

Page 14
Image 14
Marquis Everyday Hot Tub owner manual Installation instructions