Master Bilt Ice Merchandiser Maintenance Service And Analysis Guide, Malfunction, Possible Cause

Models: Ice Merchandiser

1 5
Download 5 pages 34.85 Kb
Page 4
Image 4

 

MAINTENANCE SERVICE AND ANALYSIS GUIDE

MALFUNCTION

POSSIBLE CAUSE

SOLUTION

Compressor will not start -

1.

Service cord unplugged

1.

Plug in service cord

no hum

2.

Fuse blown or removed

2.

Replace fuse

 

3.

Overload tripped

3.

Determine reasons and correct

 

4.

Control stuck open

4.

Repair or replace

 

5.

Wiring incorrect

5.

Check wiring against the diagram

Compressor will not start -

1.

Improperly wired

1.

Check wiring against the diagram

hums but trips on overload

2.

Low voltage to unit

2.

Determine reason and correct

protector

3.

Starting capacitor defective

3.

Determine reason and replace

 

4.

Relay failing to close

4.

Determine reason, correct or replace

Compressor starts and runs,

1.

Low voltage to unit

1.

Determine reason and correct

but short cycles on overload

2.

Overload defective

2.

Check current, replace overload protector

protector

3.

Excessive head pressure

3.

Check ventilation or restriction in

 

 

 

 

refrigeration system

 

4.

Compressor hot-return gas hot

4.

Check refrigerant charge, fix leak if necessary

Compressor operates long

1.

Short of refrigerant

1.

Fix leak, add charge

or continuously

2.

Control contact stuck

2.

Repair or replace

 

3.

Evaporator coil iced

3.

Determine cause, defrost manually

 

4.

Restriction in refrigeration system 4.

Determine location and remove restriction

 

5.

Dirty condenser

5.

Clean condenser

 

6.

Location too warm

6.

Ventilate area or change location.

Compressor runs fine, but

1.

Overload protector

1.

Check wiring diagram

short cycles

2.

Cold control

2.

Differential too close - widen

 

3.

Overcharge

3.

Reduce charge

 

4.

Air in system

4.

Purge and recharge

 

5.

Undercharge

5.

Fix leak, add refrigerant

Starting capacitor open,

1. Relay contacts stuck

1.

Clean contacts or replace relay

shorted or blown

2.

Low voltage to unit

2.

Determine reason and correct

 

3.

Improper relay

3.

Replace

Relay defective or burned out

1.

Incorrect relay

1.

Check and replace

 

2.

Voltage too high or too low

2.

Determine reason and correct

Refrigerated space too warm

1.

Control setting too high

1.

Reset control

 

2.

Refrigerant overcharge

2.

Purge refrigerant

 

3.

Dirty condenser

3.

Clean condenser

 

4.

Evaporator coil iced

4.

Determine reason and defrost

 

5.

Not operating

5.

Determine reason, replace if necessary

Objectionable noise

1.

Fan blade hitting fan shroud

1.

Reform or cut away small section of shroud

 

2.

Tubing rattle

2.

Locate and reform

 

3.

Vibrating fan blade

3.

Replace fan blade

 

4.

Condenser fan motor rattles

4.

Check motor bracket mounting, tighten

 

5.

General vibration

5.

Compressor suspension bolts not loosened

 

 

 

 

on applicable models - loosen them

 

6.

Worn fan motor bearings

6.

Replace fan motor

4