LIST OF PARAMETERS
Here is a list of factory set parameters the value of which can not be change in the field without the password.
Symbols | Descriptions |
| Range | M/B Setting |
| ||||
SPAt | Active Set point | 1 ÷ 2 | 1 | |
SP1 | Set Point 1 |
| SPLL ÷ SPHL | 20 |
SP2 | Set Point 2 |
| SPLL ÷ SPHL | 20 |
SEnS | Probes Type |
| Ptc - ntc | ntc |
Unit | Unit of measurement |
| °C - °F | °F |
diSP | Normal Display (Room Temperature) |
| OFF - Pr1 - Pr2 - SP - CL | Pr1 |
HSEt | Differential |
| 0 ÷ 30 °C/°F | 5 |
tonE | Compressor will run for 6 minutes |
| OFF ÷ 99.59 min.sec | 6.00 |
toFE | Then off for 4 Minutes |
| OFF ÷ 99.59 min.sec | 4.00 |
dtyP | EL = electrical Defrost |
| EL - in | EL |
dint | Defrosting interval |
| OFF ÷ 99.59 hrs.min | 6.00 |
dEFE | Max. length of defrost cycle |
| 0.01 ÷ 99.59 min.sec | 30.00 |
tEdF | Defrost stop temperature |
| - 58 ÷ 302 °C/°F | 55 |
tdCO | Compressor delay after defrost (drainage time) |
| OFF ÷ 99.59 min.sec | 2.00 |
dLo | Defrost display |
| On - OFF - Lb | lb |
FLt | High temperature fan off |
| - 58 ÷ 302 °C/°F | 45 |
PtC | Compressor protection time |
| OFF ÷ 99.59 min.sec | 1.00 |
od | Delay at power on |
| OFF ÷ 99.59 min.sec | 0.10 |
HAL | High temperature Alarm threshold |
| OFF / - 58 ÷ 302 °C/°F | 32 |
ALd | Temperature Alarms delay |
| OFF ÷ 99.59 min.sec | 30 |
ALARM SIGNALS
Message | Cause | Outputs | |
Reading Outside Range | Inputs | ||
E1 | Probe 1 bad or dis connected | Control goes into fail safe mode. Compressor on 6 minutes | |
|
| and of 4 minutes. | |
Reading Outside Range | Defrost end is timed | ||
E2 | Probe 2 bad or disconnected | Inputs | |
AL | Allarm in Progress | Outputs unchanged. | |
EEPr | Inernal Memory Error | Inputs | |
|
|
|
OTHER SIGNALS
Message
od
dEF
PdEF
CC
HI
LO
AL
AP
Reason
Delay in switching on in progress Defrosting in progress with “dLo” = Lb
Maximum temperature alarm in progress Minimum temperature alarm in progress Digital input alarm in progress
Door Open