3. Operation

3.4 Personalisation (optional)

Function

Personalisation parameters can be set and modified using the UPS Driver software installed on a computer that is connected to the UPS (see section 2.4 Connection to the RS232 communications port).

Check that the RS232 30 cable is properly connected.

UPS Driver installation:

1 - Insert the Solution-Pac CD-ROM containing the UPS Driver software in the computer drive. 2 - Open the Windows file manager or explorer and select the CD drive.

3 - Run "\Emb\Config\UPSDRVxx.exe", where xx is the software version.

It is also possible to download the UPS Driver software from the www.mgeups.com site.

Once the UPS Driver software has been installed, the parameters listed below can be modified.

"ON / OFF conditions" tab

Personalisable function

Default setting

Options

 

 

 

Automatic start

Enabled

Disabled

 

 

 

Cold start (battery power)

Enabled

Disabled

 

 

 

Forced shutdown

Enabled

Disabled

 

 

 

Sleep mode

Disabled

Enabled

 

 

 

UPS ON / OFF via software

Enabled

Disabled

 

 

 

"Battery" tab

Personalisable function

Default setting

Options

 

 

 

 

 

Once a day

Automatic "Battery test" intervals

Every weeks

Once a month

 

 

No test

 

 

 

"Low-battery warning" threshold

20% remaining battery backup time

From 0% to 100% of the remaining

 

 

battery backup time

 

 

 

Protection against deep discharges

Enabled

Disabled

 

 

 

34007532EN/AA - Page 17