MGE UPS Systems 3200C, 2200C user manual Appendices, Technical characteristics

Models: 3200C 2200C

1 28
Download 28 pages 28.83 Kb
Page 25
Image 25

6. Appendices

6.1 Technical characteristics

 

Pulsar EXtreme 2200C

 

Pulsar EXtreme 3200C

 

 

 

 

Rating

2200 VA / 1540 W

 

3200 VA / 2080 W

 

 

 

 

AC input

 

 

 

Voltage

Single phase, 120 V / 140 V / 160 V to 284 V (1)

Frequency

50/60 Hz (auto-selection)

Power factor

0.95

 

 

 

 

Output

Single phase, 230 V ± 3% (2)

Voltage

Frequency

50/60 Hz ± 5% (3)

Harmonic distortion

< 4% for linear loads, < 6% for non-linear loads

Overload capacity

110% continuous, 130% for 12 seconds, > 130% for 1.5 seconds

 

 

 

 

Battery

6 x 12 V - 7 Ah,

 

6 x 12 V - 9 Ah,

 

sealed lead-acid, maintenance free

 

sealed lead-acid, maintenance free

 

 

 

 

Environment

 

 

 

Noise level

< 50 dBA

Operating temperature

0 to 40° C

Relative humidity

20 to 90% (without condensation)

 

 

 

 

Standards and certification

 

 

 

Safety

IEC/EN 62040-1-1, EN 60950-1 (RD)

Performance

IEC/EN 62040-3

EMC

EN 50091-2/IEC 62040-2 class B

 

IEC 61000-4-2/-3/-4/-6-8/-11, IEC 61000-3-2/-3

Marking

CE, TÜV/GS, UL, cUL, CB report

 

 

 

 

(1)Values indicated for 33%, 66% and 100% of UPS rated output.

(2)Adjustable from 200 V to 250 V using UPS Driver software.

(3)Frequency-converter mode can be set using the UPS Driver software.