3. Operation
3.6 UPS remote power off
Pulsar EXtreme C is equipped with a remote power off function (RPO) that can cut power to all the devices connected to the UPS using a remote
The function is implemented by opening a contact connected to the two terminals of connector 12 on the back of the UPS.
12 | 37 | 38 |
Installation and test of the remote power off function
1 - Check that the UPS is shut off and disconnected to the
2 - Remove the RPO connector 12 by undoing the screws 37 .
3 - Connect an insulated dry contact (NC, 60 V DC, 30 V AC max., 20 mA max., cable size 0.75 mm2) to the two terminals of the RPO connector 38 .
4 - Put the RPO connector 12 back in place on the back of the UPS.
5 - Connect the UPS to the
6 - Activate the RPO external contact to test the function.
7 - To return to normal operation, deactivate the RPO external contact and restart the UPS using button 16 (press OFF, then ON).