MGE UPS Systems 1500 VA Characteristics, Pulsar EXtreme, 700 C, 1000 C, 1500 C, Mge Ups Systems

Models: 1000 VA 1500 VA 700 VA

1 4
Download 4 pages 13.75 Kb
Page 4
Image 4
Characteristics

Characteristics

Pulsar EXtreme

 

 

700 C

1000 C

 

1500 C

 

General

 

 

 

 

 

 

 

Power (Pn)

 

700 VA / 490 W

1000 VA / 700 W

1500 VA / 1050 W

Input-voltage range

 

 

120/140/160 to 276 volts without using battery power (1)

 

Frequency range

 

 

 

50/60 Hz (auto-selection)

 

 

Power factor (THDI)

 

 

 

>0.95 (< 5%)

 

 

 

Sinusoïdal output voltage

 

 

 

200/208/220/230/240 Volts

 

 

Harmonic distortion

 

 

 

<4% on linear load, <6% on non-linear load

 

 

Efficiency

 

 

85%

87%

 

88%

 

Crest factor

 

 

3:1

3:1

 

3:1

 

Short circuit current (A)

 

 

25

29

 

29

 

Overload capacity (Online mode)

 

 

 

110% permanent, 130% 12s, >130% 1.5s

 

 

Batteries

 

 

 

 

 

 

 

Backup time

 

100% Pn

50% Pn

100% Pn

50% Pn

100% Pn

50% Pn

Standard

 

7

14

7

17

6

19

Pulsar EXtreme C + 1 Pulsar EXB

 

24

47

27

59

24

79

Pulsar EXtreme C + 2 Pulsar EXB

 

41

82

47

93

43

119

Pulsar EXtreme C + 3 Pulsar EXB

 

53

124

64

136

62

168

Automatic battery test

 

 

Yes, at regular intervals without risk of interrupting protected applications

 

Communication

 

 

 

 

 

 

 

USB port

 

 

yes

yes

 

yes

 

RS232 port

 

 

yes

yes

 

yes

 

Optional cards

 

 

 

SNMP card

 

 

 

 

 

 

 

status information card

 

 

Environment

 

 

 

 

 

 

 

Acoustic noise

 

 

 

<40 dBA

 

 

 

Operating temperature

 

 

 

0 to 40°C

 

 

 

Standards and certifications

 

 

 

 

 

 

 

Performance

 

 

 

EN 50091-3/IEC 62040-3

 

 

Safety

 

 

 

EN 50091-1, EN 60950 (RD/), IEC 60950

 

 

EMC

 

 

EN 50091-2/IEC 62040-2, EN 55022/B, FCC 47 part 15 - Subpart B - Class A,

 

 

 

 

 

IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3

 

 

Marking and certifications

 

 

 

CE,TÜV/GS, UL, cUL, C-Tick

 

 

Design and manufacture

 

 

 

ISO 9001

 

 

 

Dimensions (HxWxD in mm) and Weight (Kg)

 

 

 

 

 

 

UPS (electronics + battery)

Tower

235.5x145x400

235.5x145x400

235.5x145x505

 

Rack

88(2U)x482.6x430

88(2U)x482.6x430

88(2U)x482.6x493

Electronics module

Tower/Rack

 

10/14

12/16

 

15/20

 

Battery module Pulsar EXB

Tower/Rack

 

11.5/17

15/21

 

21/27.5

 

CLA module (without batteries)

Tower/Rack

 

 

 

 

8.5/11.5

 

Warranty

 

 

 

2 years, extendable by contract

 

 

(1) values for operation at 50%, 66% and 100% rated output

 

 

 

 

 

 

 

 

 

 

 

Catalog numbers

 

EXtreme 700 C

EXtreme 1000 C

EXtreme 1500 C

Format

 

Tower

Rack

Tower

Rack

Tower

Rack

UPS

 

66345

66351

66346

66352

66347

66353

Warranty + for UPS

 

66813

66813

66818

66818

66818

66818

Pulsar EXB

 

66348

66354

66349

66355

66350

66356

Warranty + for Pulsar EXB

66813

66813

66813

66813

66813

66813

Pulsar EXtreme 1500 transformer

 

 

 

 

 

66357

 

Pulsar EXtreme 1500 CLA

 

 

 

 

 

66359

66358

Warranty + for Pulsar CLA

 

 

 

 

66818

66818

information given in this publication.

- Production: B SYLVAIN - Illustrations: Lucy in the Sky, ADN Communications.

for confirmation of the

UPS SYSTEMS, 11 2000

RS232 and USB communications ports

slot for a communication card

automatic recognition of battery extension modules

2 programmable outlets

connectors for Pulsar EXB battery extension modules

AC input connector

alarm and battery level indicators

press and hold to display percent load

lamp test or buzzer off

forced transfer to and from bypass status of programmable outlets 1 and 2

operation on bypass, in ON-LINE mode or on battery

ON/OFF

time, please ask

Publication: MGE

standards, specifications and designs change from time to

the trademarks quoted belong to their respective owners.

As All

MGE UPS SYSTEMS

140, avenue Jean Kuntzmann ZIRST - Montbonnot Saint Martin 38334 St Ismier Cedex - France Tel : (33) (0)4 76 18 30 00

MGE0384UKO

Page 4
Image 4
MGE UPS Systems 1500 VA, 700 VA, 1000 VA manual Characteristics, Pulsar EXtreme, 700 C, 1000 C, 1500 C, Mge Ups Systems