UTILITY ROUGH-IN DIMENSIONS AND POSITIONING FOR PS740-SERIES OVENS

UTILITY ROUGH-IN DIMENSIONS AND POSITIONING FOR PS740-SERIES OVENS

WARNING

DO NOT USE CONDUIT FOR GROUND CONNECTION.

CAUTION

IT IS RECOMMENDED THAT THE OVEN BE PLACED UNDER A VENTILATION HOOD FOR ADEQUATE AIR SUPPLY AND VENTILATION.

ELECTRIC SUPPLY TO BE

PROVIDED BY CUSTOMER

CIRCUIT BREAKER

Separate circuit breaker with lockout/tagout electrical shutoff for each oven. Wire each oven separately.

100 Amp circuit breaker for 208-240V, or 50 Amp circuit breaker for 380-480V.

ELECTRICAL SPECIFICATIONS

DOMESTIC: 208V main blower motors and elements,

3Ph, 75 Amp draw, 50/60 Hz, 208-240V control circuit,

3pole, 4 wire system per oven (3 hot, 1 grd).

Do NOT use conduit for ground.

or

DOMESTIC: 240V main blower motors and elements,

3Ph, 65 Amp draw, 50/60 Hz, 208-240V control circuit,

3pole, 4 wire system per oven (3 hot, 1 grd).

Do NOT use conduit for ground.

or

EXPORT: 380V elements, 3 Ph, 41 Amp draw, 50/60 Hz, 208-240V control circuit and main blower motor, 4 pole, 5 wire system per oven (3 hot, 1 neutral, 1 grd).

Do NOT use conduit for ground.

or

DOMESTIC: 480V elements, 3 Ph, 32.5 Amp draw, 50/60 Hz, 208-240V control circuit and main blower motor, 4 pole, 5 wire system per oven (3 hot, 1 neutral, 1 grd).

Do NOT use conduit for ground.

To Oven

To Oven DO NOT USE CONDUIT FOR GROUND CONNECTION.ELECTRIC SUPPLY TO BEELECTRICAL SPECIFICATIONS

Suggested dimensions are shown; utility code requirements supersede any factors shown.

Figure 2-19. Typical PS740-Series Oven(s)

Installation

ELECTRICAL RATING

27.0kW/hr.

SUPPLY WIRE

Supply wire size must be in accordance with the National Electrical Code (current edition) and must be in compliance with local codes.

NOTE: The electrical terminal connection marked “MP” located inside the control compartment is desiganated for the blue (neutral) wire to the oven. See the electrical wiring/schematics in Section 6 of this manual.

SUGGESTED

If space permits, service should be located near the control console end of the oven(s) to allow convenient access to safety switches.

P/N 60254 September 28, 2012

18