4
Input Voltage (AC Mode Function)
95-135 VAC (w/ boost) 120 VAC Models
102-135 VAC (w/o boost)
175-260 VAC (w/ boost)
220 VAC Models 190-260 VAC (w/o boost)
Boost Capability (AC Mode Function) + 12 %
5VAC per SW, (120VAC models)
Transfer Voltage Adjustment 10VAC per SW (220VAC models)
Transfer Time 2 msec typical
Input Frequency Deviation for Synchronization ± 10 %
Inrush Current 1.5x rated
Surge Protection 3 way, meets IEEE STD. 587
RFI/EMI Filtering Both Common and Normal Modes
Inverter mode (Backup Operation)
Synchronized Simulated Waveform
Sinewave Approximation
Crest Factor (Non-Linear Load) 3:1
Overload Capacity (50 msec Maximum) 3x rated
Voltage Regulation ± 5%
Frequency Regulation ± 1%
DC-to-AC Efficiency (Full Load) 75%
Overload/Short Circuit Protection Electronic and Fused
Discharged Battery Recharge Time 8 hours (95% of full charge)
Run Time See Chart