English

Symptom

Possible Cause

What To Do

 

 

 

UPS will not turn on

On/Off/Test button not

Press and release the On/Off/

 

pushed

Test button to start UPS

UPS operates in

Input AC circuit breaker is

Reset circuit breaker by

battery mode only,

tripped

pressing the plunger back in.

even though there is

 

If the AC circuit breaker trips

normal AC present

 

after UPS starts up, reduce

 

 

the load on the UPS

 

 

 

Fault LED is

UPS has detected an

Call for service

illuminated

internal fault

 

Site Wiring Fault

Incorrect service wiring

Have a Qualified Electrician

LED is illuminated

 

correct the service wiring

The AC normal

The UPS is being

Disconnect the computer

LED is illuminated,

controlled via its

cable from the UPS and press

but there is no out-

communications port

the On button. If UPS works

put

 

normally, the software has

 

 

control of the UPS

UPS does not

The batteries may be weak

Charge the batteries for 8

provide expected

or at the end of useful

hours and retest. If the runtime

runtime

service life

is still less than expected, the

 

 

batteries may need to be

 

 

replaced, even though the

 

 

Weak/Bad Battery LED is not

 

 

illuminated

Weak/Bad Battery

Weak/bad batteries or bad

Check battery connections,

LED is illuminated

connections at the battery

charge the batteries for 8

 

 

hours, replace the batteries

 

 

 

UPS occasionally

Normal operation

The UPS is performing its

emits a beep

 

intended function

 

 

 

Overload LED is

The load has exceeded the

Check the specifications (see

illuminated and a

UPS's capacity

section 8). Remove part of the

constant alarm

 

load

The Boost LED or

The UPS is in either the

The UPS is performing its

Buck LED is blink-

Boost mode or the Buck

intended function

ing.

mode

 

15

Page 16
Image 16
Minuteman UPS E1000RM1U, E1500RM1U, E700RM1U user manual Symptom Possible Cause What To Do