20

English

Default 120VAC User selectable 120/127VAC
700VA
490W 1500VA
900W
1000VA
700W
Protection
Waveform Type
Over-Current, Short-Circuit Protected and Latching Shutdown
Sine Wave
Frequency 50/60Hz, +/-0.1Hz (unless synchronized to utility)
Nominal Voltage
Maximum Power Capacity
2-6 mS Typical
>93% (Full Load)
Resettable Circuit Breaker
50 or 60 Hz, +/-6Hz, autosensing
0 - 165VAC
85 - 150VAC
120VAC: 105 - 132VAC (127VAC: 105 - 137VAC)
Transfer Time
Efficiency (Line Mode)
Input Protection
Frequency Limits
Voltage Range
Acceptable Input voltage
E1500RM1U
E1000RM1U
E700RM1U
Model Number
SYSTEM SPECIFICATIONS
Voltage Range
Topology Line-Interactive, Sine Wave
OUTPUT NON-BATTERY OPERATIONINPUT
Number of Phase Single (1 2W +G)
Nominal Voltage 120VAC
Low Voltage Transfer Point 85V resets to Utility Power at 90V or higher
High Voltage Transfer Point 150V resets to Utility Power at 145V or lower
Voltage Regulation 120VAC: -12.5% - +10% (127VAC: -17.3% - +7.8%)
Frequency Range 60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz
OUTPUT BATTERY OPERATION
Voltage Regulation Nominal +/-2% (until Low Battery Warning)
Voltage T.H.D. <5% (Linear Load)
+/-5% @ 100% Load change in 100mS
Dynamic Response
Slew Rate <1Hz/Second
Overload Capacity 110% for 20-Seconds
125% for 10-Seconds
150% Shutdown Immediately
<8% (Linear Load)