2 Product Introduction

2.1. System Overview

This On-Line UPS protects computers, servers, internetworking, and

telecommunications equipment from blackouts, brownouts, overvoltages, and

2.2.9The temperature-controlled fans will extend the life of the fans and reduce the annoying noise caused by fans.

2.3.Symbols on the LCD Display Panel

surges. This On-Line UPS converts the input AC to DC and then back to a

True Sine Wave AC output. The True Sine Wave output is regulated within

2% of the nominal output voltage. The Power Factor Correction (PFC)

circuitry corrects the input power factor to within 98% of unity and blocks the

load generated harmonic distortion from getting back on the input AC line.

This On-Line UPS provides a continuous true sine wave output with zero

transfer time and great regulation to protect your mission critical equipment.

The UPS will quietly and confidently protect your system from power

anomalies.

2.2. General Characteristics

2.2.1True On-Line architecture continuously supplies your critical equipment with a stable, regulated, transient-free, pure sine wave AC Output Power.

2.2.2The multi-functional LCD/LED panel will display various states of the UPS. The LED display will show the UPS working status, Utility Status and UPS Abnormal status. The LCD display will show the Input/Output voltage, frequency, load status, internal temperature, and faults.

2.2.3The digital control circuit enhances the ability of the UPS for remote control and monitoring.

2.2.4These UPS systems can be used in a Parallel Redundant application. To operate these UPS systems in the Parallel Redundant mode requires the Parallel Redundant kit. Contact your local distributor for more information concerning the Parallel Redundant operation.

2.2.5Maintenance Bypass Switch — which reduces down time for maintenance.

2.2.6The DC-start function allows the start-up of UPS when there is no utility power available.

2.2.7This UPS system has the Independent Battery Bypass function. The Independent Battery Bypass function allows the UPS system to provide a stable, regulated, transient-free pure sine wave AC output power even when the batteries are weak or dead.

2.2.8The battery management circuit analyses the battery discharging status to adjust the battery cut-off point and extend the life of batteries.

Item

Symbol

1LINE

2

3

4

5

6

7

8

9OFF

10BPS

11LINE OFF

12

13

14

Description

Utility or Bypass Source

Battery Low

Battery Abnormal

Output Overload

UPS working in specified mode

A Blackout Transfer occurred in UPS Output

Bypass Input Abnormal, UPS fails to transfer to Bypass, Bypass Abnormal at ECO mode

Utility Input Abnormal

UPS Shutoff

Bypass Mode

UPS Abnormal Lock

UPS Flow Chart

4 Digits Measurement Display

Indicate the item desired to be measured

4

5

Page 4
Image 4
Minuteman UPS ED6000T, ED6200T user manual Product Introduction

ED6200T, ED6000T specifications

The Minuteman UPS ED6000T and ED6200T are robust uninterruptible power supply (UPS) systems designed to offer reliable protection for sensitive electronic equipment. These units stand out in the market for their enhanced features, advanced technologies, and exceptional performance.

The core design of the ED6000T and ED6200T integrates a pure sine wave output, ensuring compatibility with all types of devices, including sensitive electronics and critical infrastructure. This feature minimizes electrical distortion, providing protection against damage from power fluctuations. They deliver up to 6000VA and 6200VA of power respectively, making them suitable for small to medium-sized data centers, telecommunications equipment, and critical servers.

One key characteristic of these models is their comprehensive LCD display that provides real-time monitoring of UPS status, battery charge level, load percentage, and other essential diagnostics. This user-friendly interface makes it convenient for users to assess performance at a glance and manage their power protection strategies effectively.

Both models employ advanced battery management technologies, including Smart Battery Management that extends battery life through optimized charging cycles. This is crucial for maintaining reliability, especially in environments where power outages can be frequent and disruptive. The UPS units also feature an automatic voltage regulation (AVR) system that corrects minor voltage fluctuations, maintaining consistent output without switching to battery mode.

Additionally, the ED6000T and ED6200T incorporate the Minuteman Green Power UPS™ technology, designed to minimize energy consumption and reduce heat output, thus contributing to lower operational costs and environmental sustainability. With an energy-efficient design, they are not only financially beneficial but also eco-friendly.

Connectivity options are another highlight, as both models feature multiple outlets, including surge-protected and battery backup outlets, ensuring plenty of connections for various devices. They are equipped with USB and serial communication ports that allow for seamless integration with monitoring and management software, thereby enhancing their functionality in networked environments.

In conclusion, the Minuteman UPS ED6000T and ED6200T are powerful solutions for businesses seeking reliable power protection. With their pure sine wave output, advanced battery management, user-friendly interfaces, and energy-efficient designs, they represent a solid investment for safeguarding critical electronics against power interruptions.