
English
(These items may require optional software or hardware)
Function  | Factory  | User Choices  | Description  | 
  | Default  | 
  | 
  | 
UPS ID | SmartSine  | Up to 64  | Use this function to uniquely  | 
  | 
  | characters  | identify the UPS in your network  | 
  | 
  | to define  | configuration  | 
  | 
  | the UPS  | 
  | 
Battery  | Date of  | Date of battery  | Enter the current date when  | 
install  | manufacture  | replacement -  | replacing batteries  | 
date  | 
  | day/month/year  | 
  | 
  | 
  | XX/XX/XXXX | 
  | 
Battery  | 1826  | Up to 5  | At first battery replacement, reset  | 
life in  | 
  | characters  | to reflect actual number of days  | 
days  | 
  | 
  | experience in your environment or  | 
  | 
  | 
  | |
  | 
  | 
  | leave factory default  | 
Enable/  | Enabled  | Enable  | When enabled, the UPS will  | 
Disable  | 
  | or  | automatically restart from a low  | 
auto  | 
  | Disable  | battery shutdown when normal AC  | 
restart  | 
  | 
  | returns  | 
Set  | Enabled  | Enabled, at  | Enabled - the UPS will emit a  | 
audible  | 
  | low battery,  | short beep when in the battery  | 
alarm  | 
  | disabled  | mode. At Low Battery the UPS  | 
state  | 
  | 
  | will emit two beeps from low  | 
  | 
  | 
  | battery warning until shutdown.  | 
  | 
  | 
  | Disabled - Use only when software  | 
  | 
  | 
  | is controlling the UPS or to  | 
  | 
  | 
  | silence the alarm  | 
Shut-  | UPS output  | UPS output  | UPS Output - When the UPS is  | 
down  | 
  | or UPS  | told to shut down, it turns off the  | 
Type  | 
  | 
  | UPS output only. UPS - Turns off  | 
  | 
  | 
  | the UPS which requires the UPS  | 
  | 
  | 
  | to be turned on manually  | 
Set  | 120VAC  | 110, 120,  | Changes output voltage during  | 
inverter  | 
  | 127VAC  | battery mode operations  | 
output  | 
  | 
  | 
  | 
voltage  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Enable/  | Disabled  | Enable  | Enabled - the UPS will be  | 
Disable  | 
  | or  | completely powered OFF and  | 
EPO | 
  | Disable  | remain OFF until EPO is disabled  | 
17