62
Parameter list
4.2 Parameter list
4.2.1 Parameter list
In the initial setting, only the simple mode parameters are displayed.
Set Pr. 160 User group read selection as required.
Parameter Name Initial
Value
Setting
Range Remarks
160 User group read
selection 0
9999 Only the simple mode parameters can be displayed.
0Simple mode and extended mode parameters can be
displayed.
1Only the parameters registered in the user group can be
displayed.
REMARKS
The parameters marked are the simple mode parameters.
The parameters marked with in the table allow its setting to be changed during operation even if "0" (initial
value) is set in Pr. 77 Parameter write selection.
Refer to the appendix 2 (page 390) for instruction codes for communication and availability of parameter clear, all clear, and
parameter copy of each parameter.
Parameters with have different specifications according to the date assembled. 400 to check the
SERIAL number.
Function Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Basic functions
0 Torque boost 0 to 30% 0.1% 6/4/3/2/
1.5/1% *1 78
1 Maximum frequency 0 to 120Hz 0.01Hz 120/60Hz
*2 87
2 Minimum frequency 0 to 120Hz 0.01Hz 0H z 87
3 Base frequency 0 to 400Hz 0.01Hz 60Hz 89
4 Multi-speed setting (high speed) 0 to 400Hz 0.01Hz 60Hz 93
5 Multi-speed setting (middle speed) 0 to 400Hz 0.01Hz 30Hz 93
6 Multi-speed setting (low speed) 0 to 40 0Hz 0.01Hz 10Hz 93
7 Acceleration time 0 to 3600/ 360s 0.1/0.01s 5s /15s *3 101
8 Deceleration time 0 to 3600/ 360s 0.1/0.01s 10s/30s *3 101
9 Electronic thermal O/L relay 0 to 500/0 to 3600A 0.01/0.1A
Rated
inverter
current
107
DC injection
brake
10 DC injection brake operation
frequency 0 to 120Hz, 9999 0.01Hz 3Hz 112
11 DC injection brake operation time 0 to 10s, 8888 0.1s 0.5s 112
12 DC injection brake operation voltage 0 to 30% 0.1% 4 /2/1% *4 11 2
13 Starting frequency 0 to 60Hz 0.01Hz 0.5Hz 104
14 Load pattern selection 0, 1 1 1 91
Jog
operation
15 Jog frequency 0 to 400Hz 0.01Hz 5Hz 95
16 Jog acceleration/deceleration time 0 to 36 00/360s 0.1/0 .01s 0.5s 95
17 MRS input selection 0, 2 1 0 124
18 High speed maximum frequency 120 to 400Hz 0.01Hz 120/60Hz
*2 87
19 Base frequency voltage 0 to 1000V, 8888, 9999 0.1V 9999 89