66
Parameter list
158 AM terminal function selection
1 to 3, 5, 6, 8 to 14, 17,
21, 24, 50, 52, 53, 67, 70,
86
11141
159
Automatic switchover frequency
range from bypass to inverter
operation
0 to 10Hz, 9999 0.01Hz 9999 293
160 User group read selection 0, 1, 9999 1 0 190
161 Frequency setting/key lock operation
selection 0, 1, 10, 11 1 0 315
Automatic restart
functions
162 Automatic restart after instantaneous
power failure selection 0, 1, 10, 11 1 0 152
163 First cushion time for restart 0 to 20s 0.1s 0s 152
164 First cushion voltage for restart 0 to 100% 0.1% 0% 152
165 Stall prevention operation level for
restart 0 to 120% 0.1% 110% 152
Current
detection
166 Output current detection signal
retention time 0 to 10s, 9999 0.1s 0.1s 135
167 Output current detection operation
selection 0, 1, 10, 11 1 0 135
168 Parameter for manufacturer setting.
Do not set.
169
Cumulative
monitor clear
170 Watt-hour meter clear 0, 10, 9999 1 9999 141
171 Operation hour meter clear 0, 9999 1 9999 141
User group
172 User group registered display/batch
clear 9999, (0 to 16) 1 0 190
173 User group registration 0 to 999, 9999 1 9999 190
174 User group clear 0 to 999, 9999 1 9999 190
Function Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting