FX2N-5A Special function block Specifications 6
6-2
Table 6.2: Power supply specificationsItem Specifications
Interface driving
power supply 24 V DC±10%, 90 mA (maximum), externally supplied
CPU driving power
supply 5 V DC, 70 mA, supplied via extension cable from PLC main unit
Table 6.3: Performance specificationsItem Specifications
Conversion speed
Channel for voltage/current input: 1 ms x Number of used channels
Channel for voltage/current output: 2 ms
(See BFM 25)
Insulation method
Photocoupler insulates the analog input/output area from PLC.
DC/DC converter insulates the power supply from analog I/O.
Channels are not insulated against each other.
Number of occupied
I/O points 8 points (including input and output points)
Applicable PLC
FX0N, FX1N, FX2N, FX2NC, FX3U, FX3UC Series PLC
For connection to the FX2NC Series PLC, an FX2NC-CNV-IF is required.
For connection to the FX3UC Series PLC, an FX2NC-CNV-IF or FX3UC-1PS-5V is
required.
Built-in memory EEPROM