Mitsubishi Electronics G-50A appendix 50A management range

Models: G-50A

1 46
Download 46 pages 54.03 Kb
Page 8
Image 8

 

Item

 

Specification

 

 

 

 

 

 

 

Group

name

Group name can be specified and display on the operation setting screen.

 

 

designation

* Group name setting is need at the initial setting.

 

 

 

 

 

 

External

Emergency stop/normal, ON/OFF, prohibit/permit for local remote operation can be

Other

 

signal input

controlled for units being controlled with a non-voltage contact signal input from an

 

interface

external source.

 

 

 

 

External

When one or more units being controlled are operating, the "ON" signal will be out-

 

 

signal output

put, and if a malfunction occurs in one or more units, the "malfunction" signal will

 

 

interface

be output.

 

 

 

Initial setting (for installation and maintenance)

 

 

Group setting

The group setting operation for units (indoor units local remote controllers, independ-

Connecting

 

ent OA processing unit, LOSSNAY and slave system controllers) are performed on

 

 

*3

the group setting screen.

information

 

 

setting

 

Interlocked

The interlocked setting for the ventilation equipment as the OA processing unit or

 

 

setting

*3

LOSSNAY , etc to indoor unit is performed on the interlocked setting screen.

 

 

 

 

 

 

Malfunction

A maximum of the 64 most recent malfunction are displayed on the malfunction log

Monitor

 

history

 

monitor.

 

Refrigerant

The connected unit address are displayed on the refrigerant monitor screen.

 

 

 

 

system monitor

 

 

 

 

 

 

 

User setting

Some of the indication and function that appear on the each screen can be specified to

 

 

match the needs of the user.

 

 

 

 

 

 

 

 

 

 

Master system

 

 

 

controller/

 

 

 

Slave system

Master/Slave setting of the system controller.

 

 

controller

* G-50A does not support slaves.

 

 

setting

*2

 

 

 

Other

 

Prohibition

The setting of a system controller which the local remote control is prohibition enable or

 

setting enable

 

 

/disable

disable.

 

 

 

 

 

The prohibited

Selecting of the prohibited controller which is only local remote controller or both

 

 

controller

local remote controller and the other system controller.

 

 

range setting

 

 

 

 

 

 

 

 

 

K-control

The system composed of K-control type air conditioner equipment can be controlled

 

 

type

*3

using the K transmission converter (PAC-SC25KAA)

*1 Each operation is available in accordance with the function of unit. *2 Master system controller and slave system controller.

G-50A management range

Another system controller management range

Unit

Unit

* G-50A does not support slaves.

M-NET Gateway management range

Management range of G-50A

Unit

Unit

When G-50A controls another system controller or when the system contains only G-50A :

G-50A is set as the master system controller.

* G-50A performs the group setting in this configuration.

When G-50A is controlled by another system controller : (Example: MJ-300Gateway)

G-50A is set as the slave system controller.

*The group setting is performed by Master system controller.

*3 OA processing unit (LOSSNAY) and the K transmission converter (PAC-SC25KAA) are not included in systems shipped to North America (USA & Canada).

-6-