3-9. DRY OPERATION
1.Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
| Room temperature minus | Room temperature minus | |||||
Thermostat | set temperature (Initial) | set temperature (During operation) | |||||
ON |
|
|
|
|
| ||
OFF | less than |
|
|
|
|
| |
|
|
|
|
| |||
|
|
2.Coil frost prevention
Coil frost prevention is as same as COOL mode.
3-10. HEAT OPERATION
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Thermostat | Room temperature minus | Room temperature minus | ||||||
set temperature (Initial) | set temperature (During operation) | |||||||
ON | less than 3.6 °F |
|
|
|
|
|
| |
|
|
|
|
|
| |||
OFF | 3.6 °F or more |
|
|
|
|
|
| |
|
|
|
|
|
| |||
3 °F | 3.6 °F | |||||||
|
|
2. High pressure protection
In HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor opera- tional frequency is controlled to prevent the condensing pressure from increasing excessively.