8 ACTUATOR CONTROL

MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA

MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA

8-1. OUTDOOR FAN MOTOR CONTROL

The fan motor turns ON/OFF, interlocking with the compressor.

[ON] The fan motor turns ON 5 seconds before the compressor starts up.

[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.

5 seconds

15 seconds

ON

Compressor

OFF

ON

Outdoor fan motor

OFF

8-2. R.V. COIL CONTROL (MUZ)

Heating . . . . . . . . . . . . . . . . . ON

Cooling . . . . . . . . . . . . . . . . . OFF

Dry . . . . . . . . . . . . . . . . . . . . OFF

NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.

<COOL><HEAT>

 

 

 

5 seconds

 

 

 

 

 

5 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R.V.coil

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor fan ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

motor

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR

 

 

 

 

 

 

 

 

 

Sensor

 

 

Purpose

 

 

 

 

 

 

 

Actuator

 

 

 

 

 

Compressor

LEV

 

 

Outdoor fan

R.V.coil

Indoor fan

 

 

 

 

 

 

 

 

 

 

 

motor

 

(MUZ)

motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge temperature

Protection

 

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor coil temperature

Cooling: Coil frost prevention

 

 

 

 

 

 

 

 

 

 

 

tion

 

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

 

 

 

 

 

Heating: High pressure protec-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost thermistor (MUZ)

Heating: Defrosting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin temperature thermistor

Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature

Cooling: Low ambient tempera-

 

 

 

 

 

 

 

thermistor

ture operation

 

 

 

 

 

 

 

 

Cooling: Low ambient tempera-

 

 

 

 

 

 

 

Outdoor heat exchanger tem-

ture operation

 

 

 

 

 

 

 

perature thermistor

tion

 

 

 

 

 

 

 

Cooling: High pressure protec-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22