8 ACTUATOR CONTROL
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds | 15 seconds |
ON
Compressor
OFF
ON
Outdoor fan motor
OFF
8-2. R.V. COIL CONTROL (MUZ)
Heating . . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The
<COOL><HEAT>
|
|
| 5 seconds |
|
|
|
|
| 5 seconds |
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Compressor | ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
R.V.coil | ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Outdoor fan ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
motor | OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||||||||||||
Sensor |
|
| Purpose |
|
|
|
|
|
|
| Actuator |
|
|
| |||||||
|
| Compressor | LEV |
|
| Outdoor fan | R.V.coil | Indoor fan | |||||||||||||
|
|
|
|
|
|
|
|
|
|
| motor |
| (MUZ) | motor | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Discharge temperature | Protection |
|
| ○ | ○ |
|
|
|
|
|
|
|
| ||||||||
thermistor |
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Indoor coil temperature | Cooling: Coil frost prevention |
|
| ○ |
|
|
|
|
|
|
|
|
| ||||||||
tion |
|
| ○ | ○ |
|
|
|
|
|
|
|
| |||||||||
thermistor |
|
|
|
|
|
|
|
|
|
| |||||||||||
Heating: High pressure protec- |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Defrost thermistor (MUZ) | Heating: Defrosting |
|
| ○ | ○ |
|
| ○ |
| ○ | ○ | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
Fin temperature thermistor | Protection |
|
| ○ |
|
|
| ○ |
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
Ambient temperature | Cooling: Low ambient tempera- |
|
| ○ | ○ |
|
| ○ |
|
|
| ||||||||||
thermistor | ture operation |
|
|
|
|
|
|
| |||||||||||||
| Cooling: Low ambient tempera- |
|
| ○ | ○ |
|
| ○ |
|
|
| ||||||||||
Outdoor heat exchanger tem- | ture operation |
|
|
|
|
|
|
| |||||||||||||
perature thermistor | tion |
|
| ○ | ○ |
|
| ○ |
|
|
| ||||||||||
Cooling: High pressure protec- |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|