33
J Check of power supply
Is there voltage 208/230 VAC
between the indoor terminal
block S1 and S2? No
Yes
Replace the indoor
electronic control P.C.
board.
Rectify indoor/outdoor
connecting wire.
Yes
If light up, OK.
If ash, refer to 10-3.
Does The upper lamp of
OPERATION INDICATOR lamp on
the indoor unit light up?
Dose LED on the inverter P.C.
board light up or ash? (Refer
to 10-6.1.) No
Replace the inverter
P.C. board.
Is there bus-bar voltage 260-325
VDC between DB61 (+) and DB61 (
–) on the inverter P.C. board?
(Refer to 10-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector (CN61)
between compressor and intelligent
power module.
Turn ON power supply and press
EMERGENCY OPERATION switch.
Inverter P.C. board
(Solder side)
DB61
260-325 VDC