1515

8ACTUATOR CONTROL

MUZ-FD09NA MUZ-FD12NA

8-2. R.V. COIL CONTROL

Heating . . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds 15 seconds

8-1. OUTDOOR FAN MOTOR CONTROL

The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.

8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR

Sensor Purpose
Actuator
Compressor
LEV Outdoor
fan motor R.V. coil Indoor fan
motor
Discharge temperature thermistor Protection ○○
Indoor coil temperature thermistor
Cooling : Coil frost prevention
Heating : High pressure protection
○○
Defrost thermistor
Cooling : High pressure protection
○○
Heating :
Defrosting ○○○○○
Fin temperature thermistor Protection ○○
Outdoor heat exchanger temperature thermistor
High pressure protection ○○○
Ambient temperature thermistor
Low ambient temperature operation
○○○
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds