3. Outdoor unit failure mode table

POWER lamp

Abnormal point

LED indication

(Indoor unit)

(Failure mode / protection)

(Outdoor P.C. board)

 

 

 

Condition

Correspondence

Indoor/

outdoor unit failure mode recall function

Outdoor unit failure mode recall function

OFF

None (Normal)

 

 

 

 

 

 

 

 

 

 

 

2-time flash

Outdoor power system

 

Overcurrent protection stop is

•Reconnect connectors.

 

 

2.5 seconds

 

 

continuously performed 3 times within

•Refer to 10-5.

"How

OFF

 

1 minute after the compressor gets

to check inverter/

 

 

started.

compressor".

 

 

 

 

 

•Check stop valve.

 

 

 

 

 

 

 

 

 

 

3-time flash

Discharge temperature

1-time flash every

Thermistor shorts or opens during

•Refer to 10-5.

"Check

 

 

2.5 seconds

thermistor

2.5 seconds

compressor running.

of outdoor thermistors".

 

 

OFF

 

 

 

Defective outdoor

 

 

Defrost thermistor

 

 

 

 

 

 

 

thermistors can be

 

 

 

 

 

 

 

 

 

 

 

 

identified by checking

 

 

 

Fin temperature thermistor

3-time flash

 

 

 

the blinking pattern of

 

 

2.5 seconds OFF

 

 

 

 

LED.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C. board temperature

4-time flash

 

 

 

 

 

 

thermistor

2.5 seconds OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature

2-time flash

 

 

 

 

 

 

thermistor

2.5 seconds OFF

 

 

 

 

 

 

 

 

 

 

 

 

4-time flash

Overcurrent

11-time flash

Large current flows into intelligent

•Reconnect compressor

 

 

2.5 seconds

 

2.5 seconds OFF

power module.

connector.

"How

 

OFF

 

 

 

•Refer to 10-5.

 

 

 

 

to check inverter/

 

 

 

 

compressor".

 

 

 

 

 

 

 

•Check stop valve.

 

 

 

 

 

 

 

 

 

 

Compressor synchronous

12-time flash

Waveform of compressor current is

•Reconnect compressor

 

 

 

abnormality (Compressor start-

2.5 seconds OFF

distorted.

connector.

"How

 

 

up failure protection)

 

 

•Refer to 10-5.

 

 

 

 

to check inverter/

 

 

 

 

compressor".

 

 

 

 

 

 

 

 

 

 

5-time flash

Discharge temperature

 

Temperature of discharge temperature

•Check refrigerant circuit

 

 

2.5 seconds

 

 

thermistor exceeds 241°F (116°C),

and refrigerant amount.

 

 

OFF

 

 

compressor stops.

•Refer to 10-5.

"Check

 

 

 

Compressor can restart if discharge

of LEV".

 

 

 

temperature thermistor reads 212°F

 

 

 

 

 

(100°C) or less 3 minutes later.

 

 

 

 

 

 

 

 

 

 

 

6-time flash

High pressure

 

Temperature of indoor coil thermistor

•Check refrigerant circuit

 

 

2.5 seconds

 

exceeds 158°F (70°C) in HEAT mode.

and refrigerant amount.

OFF

 

Temperature of defrost thermistor

•Check stop valve.

 

 

 

exceeds 158°F (70°C) in COOL mode.

 

 

 

 

 

 

 

 

 

 

7-time flash

Fin temperature/ P.C. board

7-time flash

Temperature of fin temperature

•Check around outdoor

 

 

2.5 seconds

temperature

2.5 seconds OFF

thermistor on the inverter P.C. board

unit.

 

 

 

OFF

 

 

exceeds 167 ~ 176°F (75 ~ 80°C), or

•Check outdoor unit air

 

 

 

temperature of P.C. board temperature

passage.

"Check

 

 

 

thermistor on the inverter P.C. board

•Refer to 10-5.

 

 

 

 

exceeds 158 ~ 167°F (70 ~ 75°C).

of outdoor fan motor".

 

 

 

 

 

 

 

 

 

 

8-time flash

Outdoor fan motor

 

Outdoor fan has stopped 3 times in a

•Refer to 10-5.

"Check

 

2.5 seconds

 

row within 30 seconds after outdoor fan

of outdoor fan motor".

OFF

 

start-up.

Refer to 10-5.

"Check

 

 

 

 

of inverter P.C. board".

 

 

9-time flash

Nonvolatile memory data

5-time flash

Nonvolatile memory data cannot be

•Replace the inverter

OFF

 

2.5 seconds OFF

read properly.

P.C. board.

 

2.5 seconds

 

 

 

 

10-time flash

Discharge temperature

 

Temperature of discharge temperature

•Refer to 10-5.

"Check

 

 

2.5 seconds

 

thermistor has been 122°F (50°C) or

of LEV".

 

OFF

 

less for 20 minutes.

•Check refrigerant circuit

 

 

 

 

and refrigerant amount.

 

 

 

 

 

 

 

 

 

11-time flash

DC voltage

8-time flash

DC voltage of inverter cannot be

•Refer to 10-5.

"How

 

 

2.5 seconds

 

2.5 seconds OFF

detected normally.

to check inverter/

 

OFF

 

 

 

compressor".

 

Each phase current of

9-time flash

Each phase current of compressor

 

 

compressor

2.5 seconds OFF

cannot be detected normally.

 

 

 

 

 

 

 

 

 

 

 

12-time flash

Overcurrent Compressor open-

10-time flash

Large current flows into intelligent

•Reconnect compressor

 

 

2.5 seconds

phase

2.5 seconds OFF

power module (IPM).

connector.

"How

 

 

OFF

 

 

The open-phase operation of

•Refer to 10-5.

 

 

 

 

 

compressor is detected.

to check inverter/

 

 

 

The interphase short out occurs in the

compressor".

 

 

 

 

output of the intelligent power module

 

 

 

 

 

 

(IPM).

 

 

 

 

 

 

 

The compressor winding shorts out.

 

 

 

 

 

 

 

 

 

 

 

14-time flash

Stop valve (Closed valve)

14-time flash

Closed valve is detected by compressor

•Check stop valve

OFF

 

2.5 seconds OFF

current.

 

 

2.5 seconds

 

 

 

 

 

NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).

19

Page 19
Image 19
Mitsubishi Electronics MUZ-FD12NA- U1, MUZ-FD09NA- U1 service manual Outdoor unit failure mode table

MUZ-FD09NA- U1, MUZ-FD12NA- U1, MUZ-FD12NA, MUZ-FD09NA specifications

The Mitsubishi Electronics MUZ-FD09NA is a highly efficient and versatile air conditioning unit designed for both residential and light commercial applications. This model is part of Mitsubishi's advanced range of split-system air conditioners which emphasize energy efficiency, comfort, and innovative technology.

One of the standout features of the MUZ-FD09NA is its energy efficiency. The unit boasts an impressive SEER (Seasonal Energy Efficiency Ratio) rating, which translates to reduced energy consumption and lower utility bills. This makes it an eco-friendly option for users looking to minimize their carbon footprint while enjoying comfortable indoor climates year-round.

The MUZ-FD09NA utilizes advanced inverter technology, which enables the compressor to adjust its speed based on the cooling or heating demand. This not only enhances comfort by maintaining a steady temperature but also significantly reduces energy consumption compared to traditional fixed-speed systems. Additionally, the inverter technology allows for quieter operation, making it ideal for use in bedrooms or study areas where noise can be disruptive.

For air purification, the MUZ-FD09NA is equipped with a high-efficiency filtration system that removes dust, allergens, and other particles from the air. This feature is especially beneficial for individuals with allergies or respiratory issues, ensuring cleaner and healthier indoor air quality.

In terms of user convenience, the unit comes with a user-friendly remote control, allowing for easy adjustment of settings from a distance. Some models may also offer Wi-Fi capability, enabling users to control their air conditioning unit through a smart device, even when away from home.

The MUZ-FD09NA is designed to operate in a wide range of temperatures, making it suitable for various climates. It can effectively provide cooling in the summer and heating in the winter, ensuring comfort throughout the year.

Furthermore, the unit features a compact and sleek design, allowing for easy installation in a variety of spaces without compromising aesthetics.

Overall, the Mitsubishi Electronics MUZ-FD09NA combines energy efficiency, advanced technology, and user-friendly features, making it a reliable choice for maintaining a comfortable indoor environment. Whether for residential or light commercial use, this air conditioning unit stands out as an effective solution for climate control needs.