Error Code

Abnormal point and detection method

Cause

Countermeasure

 

 

Freezing/overheating protection is

(Cooling or drying mode)

(Cooling or drying mode)

 

 

working

1 Clogged filter (reduced airflow)

1 Check clogs of the filter.

 

 

1 Freezing protection (Cooling mode)

2 Short cycle of air path

2 Remove shields.

 

 

The unit is in 6-minute resume prevention

3 Low-load (low temperature)

 

 

 

mode if pipe <liquid or condenser/evap-

operation out of the tolerance

 

 

 

orator> temperature stays under

range

 

 

 

-15:(5˚F) for 3 minutes, 3 minutes after

4 Defective indoor fan motor

4 Measure the resistance of fan motor's winding.

 

the compressor started. Abnormal if it

• Fan motor is defective.

Measure the output voltage of fan's connector

 

stays under -15:(5˚F) for 3 minutes

• Indoor controller board is

(FAN) on the indoor controller board.

 

 

again within 16 minutes after 6-minute

defective.

WThe indoor controller board should be

 

 

resume prevention mode.

 

normal when voltage of AC 208/230V is

 

 

 

 

detected while fan motor is connected.

 

 

 

 

Refer to 10-6.

 

 

 

5 Defective outdoor fan control

5 Check outdoor fan motor.

 

 

 

6 Overcharge of refrigerant

67 Check operating condition of refrigerant

 

 

7 Defective refrigerant circuit

circuit.

 

 

 

(clogs)

 

 

P6

2 Overheating protection (Heating mode)

(Heating mode)

(Heating mode)

 

 

1 Clogged filter (reduced airflow)

1 Check clogs of the filter.

 

 

The units is in 6-minute resume

2 Short cycle of air path

2 Remove shields.

 

 

prevention mode if pipe <condenser /

3 Overload (high temperature)

 

 

 

evaporator> temperature is detected as

operation beyond the tolerance

 

 

 

over 70:(158˚F) after the compressor

range

 

 

 

started. Abnormal if the temperature of

4 Defective indoor fan motor

4 Measure the resistance of fan motor's winding.

 

over 70:(158˚F) is detected again with-

• Fan motor is defective.

Measure the output voltage of fan's connector

 

in 10 minutes after 6-minute resume

• Indoor controller board is

(FAN) on the indoor controller board.

 

 

prevention mode.

defective.

WThe indoor controller board should be

 

 

 

 

normal when voltage of AC 208/230V is

 

 

 

 

detected while fan motor is connected.

 

 

 

 

Refer to 10-6.

 

 

 

5 Defective outdoor fan control

5 Check outdoor fan motor.

 

 

 

6 Overcharge of refrigerant

6~8Check operating condition of refrigerant

 

 

7 Defective refrigerant circuit

circuit.

 

 

 

(clogs)

 

 

 

 

8 Bypass circuit of outdoor unit

 

 

 

 

is defective.

 

 

 

 

 

 

 

 

Pipe temperature

1 Slight temperature difference

1~4 Check pipe <liquid or condenser /

 

 

<Cooling mode>

between indoor room

evaporator> temperature with room

 

 

Detected as abnormal when the pipe tem-

temperature and pipe <liquid

temperature display on remote controller

 

perature is not in the cooling range 3 min-

or condenser / evaporator>

and outdoor controller circuit board.

 

 

utes after compressor start and 6 minutes

temperature thermistor

Pipe <liquid or condenser / evaporator>

 

 

after the liquid or condenser/evaporator pipe

• Shortage of refrigerant

temperature display is indicated by setting

 

is out of cooling range.

• Disconnected holder of pipe

SW2 of outdoor controller circuit board as

 

Note 1) It takes at least 9 minutes to

<liquid or condenser /

follows.

 

 

detect.

evaporator> thermistor

 

)

 

Note 2) Abnormality P8 is not detected in

• Defective refrigerant circuit

Conduct temperature check with outdoor

 

drying mode.

2 Converse connection of

 

controller circuit board after connecting

 

 

 

 

Cooling range:-3 deg C[-5.4deg F]](TH-TH1)

extension pipe (on plural units

(‘A-Control Service Tool(PAC-SK52ST)’.

 

TH: Lower temperature between liquid pipe

connection)

 

 

 

temperature (TH2) and

3 Converse wiring of indoor/

23Check converse connection of extension

 

condenser/evaporator temperature

outdoor unit connecting wire

pipe or converse wiring of indoor/outdoor

 

(TH5)

(on plural units connection)

 

unit connecting wire.

 

P8

TH1: Intake temperature

4 Defective detection of indoor

 

 

 

 

<Heating mode>

room temperature and pipe

 

 

 

When 10 seconds have passed after the

<condenser / evaporator>

 

 

 

compressor starts operation and the hot

temperature thermistor

 

 

 

adjustment mode has finished, the unit is

5 Stop valve is not opened

 

 

 

detected as abnormal when

completely.

 

 

 

condenser/evaporator pipe temperature is

 

 

 

 

not in heating range within 20 minutes.

 

 

 

 

Note 3) It takes at least 27 minutes to

 

 

 

 

detect abnormality.

 

 

 

 

Note 4) It excludes the period of defrosting

 

 

 

 

(Detection restarts when defrosting

 

 

 

 

mode is over)

 

 

 

 

Heating range:3 deg C[5.4deg F][(TH5-TH1)

 

 

 

 

 

 

 

 

16

Page 16
Image 16
Mitsubishi Electronics PCA-A24GA Cause Countermeasure Freezing/overheating protection is, Working, Pipe temperature

PCA-A24GA specifications

Mitsubishi Electronics has long been a pioneer in the field of industrial automation, and the PCA-A24GA is a notable addition to its line of high-performance programmable controllers. This compact yet powerful device is designed to optimize processes and increase efficiency across various applications, making it a preferred choice for industries ranging from manufacturing to building automation.

One of the standout features of the PCA-A24GA is its versatility. The controller offers a wide range of input/output (I/O) options, enabling seamless integration with various sensors and actuators. With 24 digital input channels and 16 relay output channels, the PCA-A24GA can handle complex control tasks while maintaining a compact footprint. This flexibility is further enhanced by its support for analog inputs and outputs, allowing for greater precision in monitoring and controlling processes.

The PCA-A24GA is built with cutting-edge technologies that ensure robust performance. It employs Mitsubishi's advanced processing algorithms, which enhance real-time data processing capabilities. This ensures responsive control, reducing lag and improving overall system performance. Additionally, the controller features an intuitive programming environment, making it accessible to both seasoned engineers and those new to automation programming.

Communications are another strong suit of the PCA-A24GA. It offers multiple communication protocols, including Ethernet and RS-232, which allow for easy connectivity to various devices and systems. This ensures that the PCA-A24GA can be integrated into existing networks without significant modifications, facilitating smoother transitions and upgrades.

In terms of reliability and durability, the PCA-A24GA excels. Designed to operate in demanding environments, it is built to withstand temperature fluctuations, vibrations, and dust, which is essential for industrial settings. The controller's long operational life reduces maintenance costs and downtime, contributing to improved productivity.

Energy efficiency is also a key characteristic of the PCA-A24GA. Mitsubishi Electronics has designed this controller with eco-friendly technologies, making it suitable for organizations looking to reduce their carbon footprint while maintaining high levels of productivity.

In summary, the Mitsubishi Electronics PCA-A24GA stands out with its versatile I/O options, advanced processing capabilities, comprehensive communication protocols, and robust build. These features make it an excellent choice for industries seeking reliable and efficient automation solutions, securing Mitsubishi's reputation as a leader in the field.