S P E C I F I C A T I O N S
PLH-AAK POWER CEILING CASSETTE
Models |
|
|
|
|
|
|
|
|
| ||||||||
Function |
| Cooling |
| Heating |
| Cooling |
| Heating |
| Cooling |
| Heating |
| Cooling |
| Heating | |
Capacity | W | 7,700 |
| 8,400 |
| 9,700 |
| 10,400 |
| 12,400 |
| 14,000 |
| 14,000 |
| 16,100 | |
Total input | kW | 3.32 |
| 3.11 |
| 3.46 |
| 3.45 |
| 4.51 |
| 4.46 |
| 5.07 |
| 4.92 | |
COP | W/W | 2.32 |
| 2.70 |
| 2.80 |
| 3.01 |
| 2.75 |
| 3.14 |
| 2.76 |
| 3.27 | |
| Model name |
|
|
|
|
|
|
|
| ||||||||
| External finish |
|
|
|
|
|
| Galvanized sheets with gray heat insulation |
|
|
|
|
| ||||
| Power supply |
|
|
|
|
|
|
| Single phase, 50Hz, 240V |
|
|
|
|
| |||
| Airflow ( | l/s |
| 250 – 333 |
|
| 333 – 467 |
|
|
|
| 367 – 500 |
| ||||
Indoor unit | External static pressure | Pa ( mmAq) |
|
|
|
|
|
|
| 0 (direct blow) |
|
|
|
|
| ||
| Sound pressure level ( | dB |
| 28 – 34 |
|
| 33 – 41 |
| 35 – 43 |
|
| 37 – 45 |
| ||||
|
| W mm |
|
|
|
|
|
|
| 840 |
|
|
|
|
|
| |
| Dimensions | D mm |
|
|
|
|
|
|
| 840 |
|
|
|
|
|
| |
|
| H mm |
| 258 |
|
|
|
| 298 |
|
|
|
|
| |||
| Weight | kg |
| 24 |
|
| 30 |
| 30 |
|
| 32 |
| ||||
| External finish |
|
|
|
|
|
|
| Munsell 0.70Y 8.59/0.97 |
|
|
|
|
| |||
|
| W mm |
|
|
|
|
|
|
| 950 |
|
|
|
|
|
| |
Indoor grille | Dimensions | D mm |
|
|
|
|
|
|
| 950 |
|
|
|
|
|
| |
|
| H mm |
|
|
|
|
|
|
| 30 |
|
|
|
|
|
| |
| Weight | kg |
|
|
|
|
|
|
| 5 |
|
|
|
|
|
| |
| Model name |
|
|
|
|
|
|
|
|
| |||||||
| External finish |
|
|
|
|
|
|
| Munsell 5Y 7/1 |
|
|
|
|
| |||
| Power supply |
|
|
|
|
|
|
|
|
|
|
|
| ||||
| Refrigerant |
|
|
|
|
|
|
|
| Capillary tube |
|
|
|
|
| ||
| Compressor output | kW |
| 2.4 |
|
| 2.7 |
| 3.5 |
|
| 4.0 |
| ||||
|
|
| Internal thermostat, HP switch / |
|
|
| Thermal relay, thermal switch, HP switch, |
| |||||||||
| Protection devices |
| thermal relay, thermal switch, |
|
|
|
| ||||||||||
Outdoor unit |
|
| anti- phase protector |
|
|
|
|
|
|
|
|
|
|
|
| ||
| Airflow | l/s |
| 833 |
|
|
|
| 1,584 |
|
|
| 1,667 |
| |||
| Crankcase heater | W |
|
|
|
|
|
|
| 38 |
|
|
|
|
|
| |
| Sound pressure level | dB |
| 52 |
|
| 54 |
| 55 |
|
| 56 |
| ||||
| Sound power level | dB |
| 66 |
|
| 69 |
| 70 |
|
| 71 |
| ||||
|
| W mm |
| 870 |
|
|
|
|
|
|
| 970 |
|
| |||
| Dimensions | D mm |
| 295 + 24 |
|
|
|
|
|
|
| 345 + 24 |
|
| |||
|
| H mm |
| 850 |
|
|
|
| 1,258 |
|
|
|
|
| |||
| Weight | kg |
| 75 |
|
| 94 | 114 |
| 117 |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PKH-FAK WALL MOUNTED
Models |
|
|
|
|
|
| ||||
Function |
|
| Cooling |
| Heating |
|
| Cooling |
| Heating |
Capacity |
| W | 7,900 |
| 9,100 |
|
| 9,500 |
| 10,700 |
Total input |
| kW | 3.25 |
| 3.04 |
|
| 3.31 |
| 3.30 |
COP |
| W/W | 2.43 |
| 3.00 |
|
| 2.87 |
| 3.24 |
| Model name |
|
|
|
|
| ||||
| External finish |
|
|
|
| Munsell 3.4Y 7.7/0.8 |
|
| ||
| Power supply |
|
|
|
| Single phase, 50Hz, 240V |
|
| ||
| Airflow | l/s | 250 – 333 |
|
|
|
| 367 – 467 | ||
Indoor unit | External static pressure | Pa (mmAq) |
|
|
| 0 (direct blow) |
|
|
| |
| Sound pressure level | dB | 39 – 45 |
|
|
|
| 41 – 46 | ||
|
| W mm | 1,400 |
|
|
|
| 1,680 | ||
| Dimensions | D mm |
|
|
| 235 |
|
|
| |
|
| H mm |
|
|
| 340 |
|
|
| |
| Weight | kg | 24 |
|
|
|
| 28 | ||
| Model name |
|
|
|
|
| ||||
| External finish |
|
|
|
| Munsell 5Y 7/1 |
|
|
| |
| Power supply |
|
|
|
|
|
| |||
| Refrigerant |
|
|
|
| Capillary tube |
|
|
| |
| Compressor output | kW | 2.4 |
|
|
|
| 2.7 | ||
| Protection devices |
| Internal thermostat, HP switch/thermal relay, thermal | switch, HP switch, |
| Thermal relay, thermal switch, HP switch, | ||||
Outdoor unit |
| anti- phase protector |
|
|
| |||||
|
|
|
|
|
|
|
| |||
| Airflow | l/s | 833 |
|
|
|
| 1,584 | ||
| Crankcase heater | W |
|
|
| 38 |
|
|
| |
| Sound pressure level | dB | 52 |
|
|
|
| 54 | ||
| Sound power level | dB | 66 |
|
|
|
| 69 | ||
|
| W mm |
|
|
| 870 |
|
|
| |
| Dimensions | D mm |
|
|
| 295 + 24 |
|
|
| |
|
| H mm | 850 |
|
|
|
| 1,258 | ||
| Weight | kg | 75 |
|
|
|
| 94 |
11