Error Messages
C-170
173 Piggyback got from 68302 frame error
174 Piggyback got from 68302 noise error
175 Piggyback Config register n ot programmed properly
Error #1553: Failed configuring or diagnosing INTRAC modem (ID = %%)
The error message ID (%%) may be one of the following:
ID Description
100 RTU received irrelevant config/diagnostics ACK from piggyback
101 RTU received irrelevant config/diagnostics ACK from piggyback
102 Piggyback failed to write parameters to its int ernal eeprom
103 RTU did not receive answer about config/diagnostics from piggyback
Error #1555: Cannot operate repetition, Heap is empty
Heavy transmission traffic not necessarily on the INTRAC/MEIC only, but
because the heap serves the other MDLC channels.
Error #1557: INTRAC system table: invalid station address (StnAdr) %%
Invalid StnAdr value in the INTRAC system tables (database builder).
Possible range: 0-8191
Error #1563: INTRAC system table: invalid repeater mode (RptMod) %%
Invalid RptMod value in the INTRAC system tables (database builder).
Possible range: 0-1
Error #1564: Transmission failed: %% channel at INTRAC/MEIC port (ID = %%)
The first variable in this message is the channel name. The second (ID) may be
one of the following:
The error message ID (%%) may be one of the following:
ID Description
0 0comm module failed physical_transmit()
1 0comm module failed physical_wait(EOTX)
10 Fskadp could not transmit because CTS signal is stuck. It means that the
piggyback internal buffe r is full.
11 Fskadp could not transmit because the channel was busy
12 UART transmission timeout occurred at Fskadp module
13 ‘Wait for Holdup’ transmission timeout occurred af Fskadp
14 fskadp_warmup() was called with illegal piggyback
Error #1601: Could not identify INTRAC Modem piggyback
Problem with identifying the modem board. Possible hardware problem.