Motorola CPX8216TCPX8216T, CPX8000 manual Dual Input DC Power Distribution Panel CPX8216

Models: CPX8216T CPX8000 CPX8216TCPX8216T

1 193
Download 193 pages 10.13 Kb
Page 175
Image 175

Dual Input DC Power Distribution Panel (CPX8216)

Dual Input DC Power Distribution Panel (CPX8216)

The dual input DC version allows redundant input power supplies for full high-availability applications. It is recommended that each input source be independent of the other.

-48 VDC

-48 VDC

ON

ON

-48 VDC RTN

-48 VDC RTN

2572 9907

Figure 6-10. Dual Input DC Power Distribution Panel—Front View

Use 12 AWG or larger wire with a #10 ring terminal to connect the DC power source to the system.

Ring Terminal

WIDTH

STUD SIZE: #10

WIDTH: .490 inch (12.446 mm) or smaller

WIRE GAGE: 12AWG or bigger

Dual Breaker DC Power Distribution Panel (CPX8216)

The dual breaker 48VDC version also allows redundant input power supplies for full high-availability applications. It is recommended that each input source be independent of the other. This power distribution panel has two 30A push/pull circuit breakers and is designed for use with a Smart cable that includes breakers and additional circuitry that detect the failure of a single input DC power supply.

6

http://www.motorola.com/computer/literature

6-55

Page 175
Image 175
Motorola CPX8216TCPX8216T Dual Input DC Power Distribution Panel CPX8216, Dual Breaker DC Power Distribution Panel CPX8216