,167$//$7,21
  )/8(&211(&7,216$1'5287,1*
Connection of the coaxial flue/combustion air piping
system is in the back of the unit to the separator
tube assembly. The combustion products are ven-
ted from the boiler and condenser through the cen-
ter of the coaxial tube, while the combustion air is
supplied through the outside ring of the coaxial tube.
Since Model FCX is a condensing boiler , flue pro-
ducts exiting the unit are relatively low temperature,
from 140 - 185 deg. F (60 - 85 deg C), and saturated
with humidity. Consequently, an airtight, corrosion
resistant flue system must be provided.
Various standard option flue piping component s and
packages with which to create the flue system are
available.
P6WUDLJKW+RUL]RQWDO)OXH.LW
P$QJOHG+RUL]RQWDO)OXH.LW
3RO\SURS\OHQH39& &RQFHQWULF 9HUWLFDO
7HUPLQDO)RU)ODWRU6ORSLQJ5RRI
Useful length under sleeve tile - 16.9 inches
(0.43 m)
3RO\SURS\OHQH39& &RQFHQWULF +RUL]RQWDO
([WHQVLRQ
- joint fitting -
Useful length after assy. - 17.7 inches (0.45 m ) or
37.4 inches (0.95 m)
5HIHUHQFH /HQJWK
N40.28399 38.6 inches
(980 mm)
5HIHUHQFH V72.28414
5HIHUHQFH &RORU /HQJWK ,' 2'
N40.28393 Tile 42.5 inches
(1080mm) 3.15 inch
(80mm) 4.92 inch
(125mm)
N40.28394 Black 42.5 inches
(1080mm) 3.15 inch
(80mm) 4.92 inch
(125mm)
5HIHUHQFH /HQJWK ,' 2'
N40.28397 19.7 inches
(500 mm) 3.15 inch
(80mm) 4.92 inch
(125mm)
N40.28398 39.4 inches
(1000 mm) 3.15 inch
(80mm) 4.92 inch
(125mm)