The flue/combustion air system piping may be either horizontal or vertical or a combination of both, ob- serving the following:
•The maximum unrestricted horizontal or verti- cal flue length shall not be more than 16.4 ft (5 m).
•For each
•For each
•Horizontal runs of the flue system must pitch down 3/4 inch per yard (2 cm per m) of length towards the boiler to facilitate proper flue pro- ducts condensate drainage.
•Termination of a horizontal flue system shall not be less than 5.96 ft(1.8m) above ground unless other provisions are made to minimize the likelihood of flue/combustion air intake blockage.
•Do not place the flue terminal less than 3.3 ft. (1 m) from a ventilation hole or opening in a building.
•Termination of a vertical flue must provide at least 12 inches (30cm) above the roof jack to the combustion air intake collar.
•If there are two units in the installation with ver- tical flue systems, the termination of the sys- tems must be separated by 16 inches (40cm).
30 cm - 12 In. |
mini |
16 In. |
40 cm |
mini |
,167$//$7,21
All
Application of liquid soap over the flue pipes to be joined will aid in assembly of the parts.
Typical installation examples appear in the illustra- tion that follow.
6WUDLJKW%DODQFHG)OXH&RQILJXUDWLRQ |
|
1 in |
|
2.8 ft |
|
1,80 m | 5.9 ft. |
Option: Straight Horizontal Flue Kit
$QJOHG%DODQFHG)OXH&RQILJXUDWLRQ |
|
1 in |
|
1,80 m | 5.9 ft. |