DCA-45SSIU3 (60 Hz) — INSTALLATION

Outdoor Installation

Install the generator in a area that is free of debris, bystanders, and overhead obstructions. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.

CAUTION - EXHAUST HAZARD

Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

Indoor Installation

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside.The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

Mounting

The generator must be mounted on a solid foundation (such as concrete) and set firmly on the foundation to isolate vibration of the generator when it is running. The generator must set at least 6 inches above the floor or grade level (in accordance to NFPA 110, Chapter 5-4.1). DO NOT remove the metal skids on the bottom of the generator. They are to resist damage to the bottom of the generator and to maintain alignment.

Generator Grounding

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground. See Figure 4 for a typical grounding configuration.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 10 AWG (5.3 mm2) or larger.

b.Aluminum - 8 AWG (8.4 mm2) or larger.

2.When grounding the generator (Figure 4) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried aminimum of 8 ft. into the ground.

When connecting the generator

NOTEto any buildings electrical system ALWAYS consult with a licensed electrician.

DCA-45SSIU3 (60 Hz) — OPERATION AND PARTS MANUAL — REV. #0 (11/30/05) — PAGE 17

Page 17
Image 17
Multiquip operation manual DCA-45SSIU3 60 Hz Installation, Outdoor Installation, Indoor Installation, Mounting

DCA-45SSIU3 specifications

The Multiquip DCA-45SSIU3 is a robust and versatile diesel generator designed to provide reliable power for various applications, making it an essential piece of equipment for construction sites, events, and emergency backup. This generator is renowned for its efficiency, durability, and user-friendly design, catering to a wide range of power needs while ensuring optimal performance.

One of the standout features of the DCA-45SSIU3 is its powerful 45 kVA output. This generator is powered by a reliable and fuel-efficient Yanmar diesel engine, which not only delivers consistent power but also ensures lower emissions, making it an environmentally friendly choice for power generation. With its high fuel efficiency, operators can expect longer run times between refuels, reducing downtime and increasing productivity on the job site.

The DCA-45SSIU3 boasts a compact and mobile design, equipped with a durable steel frame and a weather-resistant enclosure. This ensures that the generator can withstand harsh outdoor conditions while providing easy access for maintenance and operation. Its built-in forklift channels and lifting eyes enhance its portability, allowing for simple relocation to different job sites.

This generator is equipped with advanced technologies that enhance its performance and safety. The intuitive control panel features easy-to-read gauges and indicators for monitoring performance. Users can quickly access essential functions, including start/stop controls and circuit breaker protections, which safeguard the generator from overloads. Additionally, its automatic voltage regulation delivers stable power, ensuring that sensitive electronic equipment runs smoothly without risk of damage.

The DCA-45SSIU3 also includes a fuel tank designed for extended operation, with a capacity that provides significant hours of runtime. This feature is complemented by an efficient cooling system that maintains optimal engine temperatures, ensuring reliability even during prolonged usage.

In summary, the Multiquip DCA-45SSIU3 is a powerful and dependable generator that meets the demands of diverse applications. Its robust design, combined with advanced features and efficiency, makes it an ideal choice for contractors, event planners, and anyone needing reliable backup power. With a reputation for performance and longevity, this generator stands out in the competitive market of portable power solutions.