DCA-45SSIU3 (60 Hz) — OPERATION AND PARTS MANUAL — REV. #0 (11/30/05) — PAGE 29
1
Figure 28. Output Terminal Lugs
3Ø 480/277V Connections
2. Connect the load wires to the
Output Terminal Lugs
as
shown in Figure 28.
Figure 30. Output Terminal Lugs
1Ø-240V/120V Connections
DCA-45SSIU3 (60 Hz) — OUTPUT TERMINAL PANEL CONNECTIONS
Figure 27. Voltage Selector Switch 480/277V
Three-Phase Position
3Ø 480/277 Output Terminal Lug Voltages
1. Place the voltage selector switch in the 3Ø 480/277
position as shown in Figure 27.
3. Turn the voltage regulator knob (Figure 24) clockwise to
increase voltage output, turn counterclockwise to
decrease voltage output.
1Ø 240V/120V Output Terminal Lug Voltages
1. Place the voltage selector switch in the 1Ø 240/120
position as shown in Figure 29.
2. Connect the load wires to the
Output Terminal Lugs
as
shown in (Figure 30).
Figure 29. Voltage Selector Switch 240/120V
Single-Phase Position
3. Turn the voltage regulator knob (Figure 24) clockwise to
increase voltage output, turn counterclockwise to
decrease voltage output.