inspection/SETUP

Day-to-day addition of coolant is done from the recovery tank.When adding coolant to the radiator, DO NOT remove the radiator cap until the unit has completely cooled. See Table 10 for engine, radiator, and recovery tank coolant capacities. Make sure the coolant level in the recovery tank is always between the “H” and the “L” markings.

Table 10. Coolant Capacity

Engine and Radiator

1.74 gal (606 liters)

Reserve Tank

0.26 gal. (1 liter)

Operation in Freezing Weather

When operating in freezing weather, be certain the proper amount of antifreeze (Table 11) has been added.

Table 11. Anti-Freeze Operating Temperatures

Vol %

Freezing Point

Boiling Point

Anti-

 

 

 

 

°C

°F

°C

°F

Freeze

 

 

 

 

50

-37

-34

108

226

 

 

 

 

 

NOTICE

When the antifreeze is mixed with water, the antifreeze mixing ratio must be less than 50%.

Cleaning the Radiator

The engine may overheat if the radiator fins become overloaded with dust or debris. Periodically clean the radiator fins with compressed air. Cleaning inside the machine is dangerous, so clean only with the engine turned off and the negative battery terminal disconnected.

Air Cleaner

Periodic cleaning/replacement is necessary. Inspect it in accordance with the ISUZU Engine Owner’s Manual.

Fan Belt Tension

A slack fan belt may contribute to overheating, or to insufficient charging of the battery. Inspect the fan belt for

damage and wear and adjust it in accordance with the

ISUZU Engine Owner’s Manual.

The fan belt tension is proper if the fan belt bends 10 to 15

mm(Figure 22) when depressed with the thumb as shown below.

Figure 22. Fan Belt Tension

CAUTION

NEVER place hands near the belts or fan while the generator set is running.

Battery

This unit is of negative ground DO NOT connect in reverse. Always maintain battery fluid level between the specified marks. Battery life will be shortened, if the fluid level are not properly maintained. Add only distilled water when replenishment is necessary.

DO NOT over fill. Check to see whether the battery cables are loose. Poor contact may result in poor starting or malfunctions. Always keep the terminals firmly tightened. Coating the terminals with an approved battery terminal treatment compound. Replace battery with only recommended type battery.

The battery is sufficiently charged if the specific gravity of the battery fluid is 1.28 (at 68° F). If the specific gravity should fall to 1.245 or lower, it indicates that the battery is dead and needs to be recharged or replaced.

Before charging the battery with an external electric source, be sure to disconnect the battery cables.

DCA20spxu2 servpro® • operation and parts manual — rev. #0 (09/23/13) — page 29