LOAD APPLICATION

SINGLE PHASE LOAD

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is infl uenced by the effi ciency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

THREE PHASE LOAD

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fl uorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA300SSC GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (06/25/09) — PAGE 25

Page 25
Image 25
Multiquip DCA300SSC manual Load Application, Single Phase Load, Three Phase Load

DCA300SSC specifications

The Multiquip DCA300SSC is a durable and powerful skid-mounted diesel generator designed for a range of applications, including construction sites, events, and emergency backup power. With a robust operational capacity of 300 kilowatts, this generator stands out for its reliability and efficiency in providing continuous power.

One of the key features of the DCA300SSC is its commercial-grade engine. The generator is equipped with a reliable and efficient diesel engine that ensures optimal performance under various operating conditions. This engine is designed for durability and longevity, minimizing the need for frequent maintenance. The generator's high fuel efficiency reduces operational costs, making it an economical choice for businesses and contractors.

Another notable characteristic of the DCA300SSC is its advanced sound attenuation technology. This design feature significantly lowers noise levels during operation, which is essential for applications in populated areas or sensitive environments. The generator is housed in a weather-resistant enclosure that protects it from environmental factors, ensuring consistent performance regardless of weather conditions.

In terms of power management, the DCA300SSC is equipped with a sophisticated digital control panel that allows users to monitor and manage the generator’s performance effectively. The control panel displays vital information, such as voltage, frequency, and run-time hours, facilitating easy operation and troubleshooting. This technology also integrates automatic voltage regulation, enhancing the generator's stability and safety during operation.

Safety is a priority in the design of the DCA300SSC. It is built with multiple safety features, including low oil pressure shutdown, high coolant temperature shutdown, and over-speed protection. These measures provide peace of mind to users by reducing the risk of equipment failure and ensuring safe operation.

The compact design and skid-mounted configuration of the DCA300SSC allow for easy transport and installation, making it a versatile solution for a variety of industries. Additionally, the generator can be configured for different voltage outputs, further increasing its adaptability for specific applications.

In summary, the Multiquip DCA300SSC is a powerful and versatile generator known for its reliability, efficiency, and advanced features. With its durable construction, advanced sound attenuation, user-friendly control panel, and robust safety features, it meets the demands of both commercial and industrial applications with ease. Whether for temporary power supply or backup generation, the DCA300SSC is a suitable choice for professionals seeking dependable energy solutions.