GENERATOR START-UP PROCEDURE (MANUAL)

BEFORE STARTING

CAUTION

The engine’s exhaust contains harmful emissions.

ALWAYS have adequate ventilation when operating. Direct exhaust away from nearby personnel.

WARNING

NEVER manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.

1.Place the main,G.F.C.I.,and aux. circuit breakers (Figure 35) in the OFF position prior to starting the engine.

Figure 35. Main, Aux. and GFCI

Circuit Breakers (OFF)

2.Make sure the voltage change-over board has been confi gured for the desired output voltage.

3.Connect the load to the receptacles or the output terminal lugs as shown in Figure 10. These load connection points can be found on the output terminal panel and the output terminal panel’s hard wire hookup panel.

4.Tighten terminal nuts securely to prevent load wires from slipping out.

5.Close all engine enclosure doors (Figure 36).

CORRECT INCORRECT

Figure 36. Engine Enclosure Doors

STARTING (MANUAL)

1.Place the engine speed switch (Figure 37) in the LOW (down) position.

Figure 37. Engine Speed Switch (Low)

2.Place the MPEC control switch in the MANUAL position to start the engine (Figure 38).

Figure 38. MPEC Control Switch

(Manual Position)

3.Depending on the temperature of the coolant (cold weather conditions), the pre-heat lamp (Figure 39) will light (ON) and remain on until the pre-heating cycle has been completed. After completion of the pre-heating cycle, the light will go OFF and the engine will start up automatically.

Figure 39. Pre-Heat Button

4.Once the engine starts, let the engine run for 1-2 minutes. Listen for any abnormal noises. If any abnormalities exist, shut down the engine and correct the problem. If the engine is running smoothly, place the engine speed switch (Figure 40) in the HIGH (up) position.

Figure 40. Engine Speed Switch (High)

5.Verify that the engine running status LED on the MPEC unit (Figure 41) is ON (lit) after the engine has been started.

Figure 41. Engine Running LED (ON)

PAGE 34 — DCA300SSC GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (06/25/09)

Page 34
Image 34
Multiquip DCA300SSC manual Generator START-UP Procedure Manual, Before Starting, Starting Manual

DCA300SSC specifications

The Multiquip DCA300SSC is a durable and powerful skid-mounted diesel generator designed for a range of applications, including construction sites, events, and emergency backup power. With a robust operational capacity of 300 kilowatts, this generator stands out for its reliability and efficiency in providing continuous power.

One of the key features of the DCA300SSC is its commercial-grade engine. The generator is equipped with a reliable and efficient diesel engine that ensures optimal performance under various operating conditions. This engine is designed for durability and longevity, minimizing the need for frequent maintenance. The generator's high fuel efficiency reduces operational costs, making it an economical choice for businesses and contractors.

Another notable characteristic of the DCA300SSC is its advanced sound attenuation technology. This design feature significantly lowers noise levels during operation, which is essential for applications in populated areas or sensitive environments. The generator is housed in a weather-resistant enclosure that protects it from environmental factors, ensuring consistent performance regardless of weather conditions.

In terms of power management, the DCA300SSC is equipped with a sophisticated digital control panel that allows users to monitor and manage the generator’s performance effectively. The control panel displays vital information, such as voltage, frequency, and run-time hours, facilitating easy operation and troubleshooting. This technology also integrates automatic voltage regulation, enhancing the generator's stability and safety during operation.

Safety is a priority in the design of the DCA300SSC. It is built with multiple safety features, including low oil pressure shutdown, high coolant temperature shutdown, and over-speed protection. These measures provide peace of mind to users by reducing the risk of equipment failure and ensuring safe operation.

The compact design and skid-mounted configuration of the DCA300SSC allow for easy transport and installation, making it a versatile solution for a variety of industries. Additionally, the generator can be configured for different voltage outputs, further increasing its adaptability for specific applications.

In summary, the Multiquip DCA300SSC is a powerful and versatile generator known for its reliability, efficiency, and advanced features. With its durable construction, advanced sound attenuation, user-friendly control panel, and robust safety features, it meets the demands of both commercial and industrial applications with ease. Whether for temporary power supply or backup generation, the DCA300SSC is a suitable choice for professionals seeking dependable energy solutions.