Load Application

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

„„When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

„„When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

„„When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA45SSIU4 60 hz Generator • operation and parts manual — rev. #1 (10/24/13) — page 25

Page 25
Image 25
Multiquip dca45ssiu4 manual Load Application, Single Phase Load, Three Phase Load, Type of Load

dca45ssiu4 specifications

The Multiquip DCA45SSIU4 is a robust and versatile diesel generator designed to meet the demands of various applications, ranging from construction sites to emergency power backup. With a powerful engine and a comprehensive array of features, this generator is engineered to deliver reliable performance and fuel efficiency.

At the heart of the DCA45SSIU4 is its 45 kVA output capability, which is powered by a highly efficient Yanmar engine. This engine not only provides ample power but also features advanced emissions technology that meets stringent environmental regulations. Users can rely on the DCA45SSIU4 for consistent energy delivery while minimizing their carbon footprint, making it a great choice for eco-conscious projects.

One of the standout features of the DCA45SSIU4 is its compact design. The generator is housed within a durable weatherproof enclosure that ensures reliable operation in various conditions. The enclosure is sound attenuated, significantly reducing noise levels, which is critical for projects in urban or noise-sensitive areas. This design allows the generator to operate quietly without disturbing the surrounding environment.

The DCA45SSIU4 is equipped with state-of-the-art digital control technology, featuring an intuitive user interface that simplifies monitoring and operation. This control panel includes essential indicators for voltage, frequency, and running hours, enabling users to track performance and maintenance needs efficiently. The generator also has a built-in automatic start/stop function, which activates the unit when power is needed and turns it off when it is not, thus enhancing convenience and saving fuel.

Another notable characteristic is its versatility in fuel efficiency. The DCA45SSIU4 can operate for extended periods on a single tank of diesel, making it ideal for both short-term and long-term power needs. Additionally, its features include a robust frame with forklift pockets and lifting points, ensuring easy transportation and setup at job sites.

In conclusion, the Multiquip DCA45SSIU4 combines power, durability, and advanced technology, positioning itself as an excellent solution for anyone in need of reliable temporary or backup power. Its features, including a powerful Yanmar engine, compact design, digital control technology, and exceptional fuel efficiency, make it a top choice for professionals across various industries. Whether for construction, events, or emergency situations, the DCA45SSIU4 stands out as a dependable generator that meets modern demands.