GA-3.6RZ3 — PRE-SETUP

General Inspection Prior to Operation

This generator has been thoroughly inspected and accepted prior to shipment from the factory. However, be sure to check for damaged parts or components, or loose nuts and bolts, which could have occurred in transit.

GA-3.6RZ3PRE-SETUP

Circuit Breaker

A 2-pole, 12.5 amp circuit breaker is provided on the control box to protect the generator from an overload. Make sure to switch the circuit breakers to the "OFF" position prior to starting the engine.

Ground

The nut and ground terminal on the generator should always be used to connect the generator to a suitable ground. The ground path should be of #8 size wire.

Connect the terminal of the ground wire between the lock washer and the nut and tighten the nut fully. Connect the other end of this wire to a suitable ground.

Extension Cable

When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generator and point of use (load) is held to a minimum. Use the cable selection chart (Table 2 ) as a guide for selecting proper cable size.

Table 2. Cable Selection (60 Hz, single phase operation)

Current

Load In Watts

Maximum Allowable Cable Length

in

 

 

 

 

 

 

At 120

At 240

#10 Wire

#12 Wire

#14 Wire

#16 Wire

Amperes

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

250 ft.

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

125 ft.

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

100 ft.

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

PAGE 12 — GA-3.6RZ3 A.C. GENERATOR— PARTS & OPERATION MANUAL — REV. #3 (09/03/04)